Plan Review Notes
Plan Review Notes For Permit 08110178
Permit Number 08110178
Review Stop B
Sequence Number 3
Notes
Date Text
2009-03-31 15:19:01BUILDING PLAN REVIEW
 PERMIT: 08110178
 ADD:6901 OKEECHOBEE BLVD SUITE D19, D23 & E1.
 CONT: "PLAN REVIEW"
 TEL: (262)901-0505 EXT 110
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND MAJOR WORKING DRAWING REVIEW/ PLAN REVIEW
 ACTION: DENIED
 MARCH 31/2009
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) COMPLIED.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER MAARCH 1/2009 SHALL BE REVIEWED TO
 THE 2007 FBC BUILDING WITH THE 2009 SUPPLEMENTS & 2007
 EXISTING BUILDING CODE WITH 2009 SUPPLEMENTS. PLEASE
 PROVIDE AS TO WHAT LEVEL OF ALTERATIONS WILL BE
 COMPLETED UNDER THIS PERMIT. 2007 EXIST FBC 101.5
 COMPLIANCE METHODS. THE REPAIRS, ALTERATIONS, CHANGE IN
 OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING
 METHODS LISTED IN SECTION 101.5.1 THROUGH 101.5.3 AS
 SELECTED BY THE APPLICANT.
  
 2) COMPLIED.
  
 3-4) COMPLIED.
  
 5) SEMI-COMPLIED. MISSING WIND DESIGN INFORMATION FOR
 ROOF TOP EQUIPMENT.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR). THE CITY OF WEST PALM BEACH IS LOCATED IN A
 140 MPH WIND-BORNE DEBRIS REGION.
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR
 THE SELECTION OF EXTERIOR COMPONENTS AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 6) COMPLIED.
  
 7) 2ND REQUEST, PLEASE SEE MECHANICAL COMMENT# 3 ABOUT
 THE ROOF TOP EQUIPMENT BEING REQUIRED TO MEET WIND
 PRESSURES, FBCM 301.13.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.