| 2009-03-27 11:23:07 | REVIEW #: 2ND **PLAN CHECK ONLY** |
| | ACTION: DENIED |
| | |
| | THIS PROJECT REVIEWED FOR COMPLIANCE WITH THE FOLLOWING |
| | CODES: |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: PLANS STILL SUBMITTED FOR PLAN REVIEW WITH NO |
| | PERMIT APPLICATION. PLANS ARE NOW SUBJECT TO THE |
| | REQUIREMENTS OF THE 2007 FLORIDA BUILDING CODE WHICH |
| | WENT INTO EFFECT ON MARCH 1, 2009. PLANS WILL REMAIN IN |
| | FAIL STATUS PENDING SUBMISSION OF AN ACTUAL PERMIT |
| | APPLICATION. |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. **PREVIOUS COMMENT**PLANS CALL FOR NEW RTU AND |
| | EXHAUST FAN TO BE INSTALLED ON ROOF. NO INFORMATION |
| | COULD BE FOUND ON PLANS REGARDING WIND RESISTANCE. |
| | MECHANICAL APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH FBCB SECTION 1609 PER |
| | FBCM 301.13. PROVIDE ATTACHMENT DETAIL SHOWING ROOF |
| | CURBS TO BUILDING STRUCTURE AND RTU/EF TO ROOF CURB |
| | ATTACHMENTS. ALSO, PLEASE PROVIDE MANUFACTURER'S DATA |
| | SHOWING THESE APPLIANCES ARE DESIGNED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH THIS SECTION. |
| | **NOT ADDRESSED**: THE WIND LOAD CALCULATIONS PROVIDED |
| | ARE FOR THE ATTACHMENT OF THE RTU TO THE ROOF AND DO |
| | NOT PROVIDE INFORMATION REGARDING THE WIND RESISTANCE |
| | CAPABILITIES OF THE RTU ITSELF. PLEASE SHOW COMPLIANCE |
| | WITH FBC-M 301.12. ALSO, THE MANUFACTURER'S DATA FOR |
| | THE ROOTOP FAN INDICATE THE FAN IS DESIGNED FOR 130 MPH |
| | WINDS. ACCORDING TO THE WIND MAPS FOUND INH FBC-B 1609, |
| | THE CITY OF WEST PALM BEACH IS IN THE 140 MPH WIND |
| | ZONE. FAN SHALL BE DESIGNED FOR THE PROPER WIND ZONE IN |
| | ACCORDANCE WITH THESE SECTIONS. |
| | NOTE: ALL WIND RESISTANCE DOCUMENTATION PROVIDED WILL |
| | BE REVIEWED BY THE BUILDING (STRUCTURAL) PLANS |
| | EXAMINER. |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. OK |
| | |
| | 7. OK |
| | |
| | NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH |
| | INFORMATION ON HOW EACH COMMENT WAS ADDRESSED AND WHERE |
| | THE RELEVANT INFOAMTION CAN BE FOUND. THIS WILL HELP TO |
| | FACILITATE A TIMELY REVIEW UPON RESUBMISSION. |
| | |