Plan Review Notes
Plan Review Notes For Permit 08110178
Permit Number 08110178
Review Stop E
Sequence Number 2
Notes
Date Text
2009-03-26 13:07:19** DENIED REVIEW **
  
 1) NOTE: AS NOTED ON THE PREVIOUS REVIEW ON THE FIRST
 COMMENT. IT IS IMPORTANT TO KNOW THAT PLANS WERE ONLY
 SUBMITTED FOR PLAN REVIEW ONLY. THIS DOES NOT *LOCK* A
 PROJECT UNDER ANY SPECIFIC CODE EDITIONS UNLESS PERMIT
 APPLICATION IS MADE. AS THE PROJECT WAS ONLY SUBMITTED
 FOR PLAN REVIEW AND IS DESIGNED UNDER THE 2004 FBC THIS
 DID NOT LOCK PROJECT UNDER THE 2004 FBC. AS OF MARCH 1,
 2009 THE STATE OF FLORIDA UNDER FS 553.73 HAS ADOPTED
 THE 2007 FBC WITH 2009 REVISIONS.
 PLEASE ALSO KNOW SOME OTHER CODES SUCH AS THE LIFE
 SAFETY CODE AND STATE FIRE CODE WERE ALSO REVISED PER
 FLORIDA ADMINISTRATIVE CODE 69A-60.003 AND .004 BY THE
 STATE FIRE MARSHAL.
 THE FOLLOWING CODES NEED TO BE ON PLANS. PLEASE BE SURE
 THE FOLLOWING ARE ON ELECTRICAL AS WELL. SOME CODES
 STATED ON PLANS ARE OK AND IN EFFECT. PLEASE BE SURE
 THE FOLLOWING ARE UPDATED ON ALL RELEVANT SHEETS.
  
 2007 FBC W/2009 REVISIONS.
 2006 NFPA-101
 2006 NFPA-1
 OTHER CODES SUCH AS 2002 NFPA-72, 2005 NFPA-70 ARE
 STILL ACCURATE.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO FBC
 AND CHAPTER 13 FOR LIGHTING PERFORMANCE CALCULATIONS.
 THE SUBMITTED DOCUMENTS FROM COMCHECK ARE NOT ADOPTED
 BY THE FLORIDA BUILDING CODE OR PERMITTED IN THE STATE
 OF FLORIDA. THE PREVIOUS CODE SECTIONS GIVEN WERE
 STATED BASED ON THE CODE IN EFFECT AT THE TIME OF THE
 PLAN REVIEW SUBMISSION. SINCE THAT TIME AS STATED IN
 NOTE #1, THE STATE HAS ADOPTED A NEW CODE.
 PLEASE SEE FBC CHAPTER 13 2007 EDITION WITH 2009 GLITCH
 AMENDMENTS. THIS CHAPTER WAS COMPLETELY REVISED FROM
 THE FIRST PRINTING OF THE 2007 FBC. THERE ARE
 SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT.
 ** PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.AB.5, 13-415.AB.5.1, 13-415.B
 THESE SECTIONS FOR LIGHTING PERFORMANCE CALCULATIONS
 HAVE BEEN COMPLETELY REVISED.
  
 ** ONCE AGAIN THE SUBMITTED COMCHECK CALCULATIONS ARE
 NOT PERMITTED AND CAN NOT BE USED IN THE STATE OF
 FLORIDA. ONE COPY HAS BEEN RETAINED BY THIS OFFICE.
  
 ** IT IS ALSO IMPORTANT TO KNOW THAT THE INPUT DATA
 REPORT WHICH WILL ACCOMPANY THE SUBMITTED ENERGY
 CALCULATIONS MUST COORDINATE WITH ALL COMPONENTS OF
 CONSTRUCTION AS SHOWN ON PLANS. THIS INCLUDES ALL
 LIGHTING FROM PLANS, FIXTURE LEGEND ETC.
  
 3) NOTE: AS STATED IN PREVIOUS REVIEW PLEASE SUBMIT AND
 SHOW LIGHTING CONTROLS MEETING MINIMUM CODE COMPLIANCE.
 THE RESPONSE MENTIONS TO SEE 210 AND 220 HOWEVER THE
 ONLY ITEM ON THOSE SHEETS ARE NOTES TO PROVIDE A SYSTEM
 OF SOME SORT. PLACING A NOTE ON PLANS IN LIEU OF ACTUAL
 DETAILS OR DESIGN OF A CODE COMPLIANT SYSTEM IS NOT
 PERMITTED. MUST SHOW CODE COMPLIANCE. PLEASE KNOW THE
 CODE SECTIONS UNDER THE 2007 FBC HAVE NOW BEEN REVISED.
 PLEASE SEE THE FOLLOWING SECTIONS. 13-415.AB.1.1, .1.2
 AND .1.3
  
  
 4) NOTE: THIS IS A NEW NOTE: BY DEFINITIONS IN THE FBC,
 ARE THESE TWO SEPARATE BUILDINGS? IS THE WALL WITH NEW
 OPENINGS A FIRE WALL? PLEASE SEE DEFINITIONS OF FIRE
 WALL.
 IF THESE ARE TWO SEPARATE BUILDINGS, ON TWO SEPARATE
 SERVICES AND NOW BECOMING ONE BUILDING THEN SOME
 CLARIFICATION AND CHANGES IN DOCUMENTS MAY BE NEEDED.
 THERE CAN BE OPENINGS IN FIRE WALLS HOWEVER THERE ARE
 REQUIREMENTS FOR OTHERS TRADES INCLUDING ELECTRICAL.
 PLEASE PROVIDE THE COMPLETE RISER DIAGRAM FOR ALL
 SERVICE EQUIPMENT ON THESE BUILDINGS. THE WALMART WHICH
 IS LOCATED IN THIS SAME SHOPPING CENTER IS A SEPARATE
 BUILDING WITH FIRE WALL SEPARATION AND IS NOT PART OF
 THESE TWO BUILDINGS. THE WALMART SECTION IS NOT PART OF
 THIS QUESTION.
 BASED ON THE ARCHITECTURAL SHEETS THESE APPEAR TO BE
 POSSIBLY BE TWO BUILDINGS WHICH EXIST BEING MADE INTO
 ONE.
 BASED ON RISER THERE SEEMS TO BE TWO SEPARATE
 ELECTRICAL SERVICES WHICH WOULD NOW BE FED FROM ONE
 GENERATOR.
 BONDING OF SERVICES, ETC ARE NOT KNOWN.
 THERE IS A 400 AMP BREAKER FEEDING NEW ATS TO PANEL D
 HOWEVER THE CONDUCTORS AS SHOWN ARE ONLY RATED FOR
 200AMPS. 310.16, 240.4 RISER DOES NOT INDICATE PARALLEL
 FEEDERS.
  
 *** PLEASE GO OVER DESIGNS FOR MINIMUM CODE COMPLIANCE.
  
 ** ONCE AGAIN THERE ARE SOME ITEMS NOT SUBMITTED OR
 KNOW AT THIS TIME AND THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
 ONE SET OF PLANS FOR ELECTRICAL WILL ALSO BE RETAINED
 BY THIS OFFICE.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  