Plan Review Notes
Plan Review Notes For Permit 08110178
Permit Number 08110178
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-05 15:52:46PLAN REVIEW DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 EXISTING BUILDING CODE
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SHT "T" THE DESIGN CRITERIA SHALL INCLUDE THE 2005,
 2006 & 2007 REVISIONS TO THE 2004 FLORIDA BUILDING
 CODE. SECTION 106.1.1.
  
 2. SHT "T" INDICATE THE LEVEL OF ALTERATION AS REQUIRED
 IN CHAPTER 3 OF THE FBC-2004 EXISTING BUILDING CODE.
  
 3. SHT "T" AN IMPRESSION TYPE SEALING COMPLYING WITH
 FAC 61G1-16.001, 61G1-16.002 & FS 481.2055 IS REQUIRED.
 STAMP TYPE SEALS ARE NOT APPROVED.
  
 4. ALL SHEETS REQUIRE THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING FIRM, (APPLIED FOR - SEE
 ATTACHED SHEET), AND FOR THE ARCHITECT, (NOT FOUND), IN
 THE TITLE BLOCK OF EACH SHEET. FAC 61G15-23.002,
 61G1-16.004(2) & FS 471.025, 481.219, 481.2055.
  
 5. ALL SHEETS REQUIRE THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENTS. FAC 61G1-16.004(6), FAC
 61G15-23.002(2) & FS 471.025 & 481.2055.
  
 6. THE SEAL AFFIXED TO THE SHEETS IS NOT APPROVED. SEAL
 SHALL BE APPROXIMATELY 2 INCHES IN DIAMETER. ALSO THE
 ARCHITECTURAL NUMBER ON THE SEAL, AR90016025 DOES NOT
 REFLECT THE NUMBER INDICATED ON THE STATE OF FLORIDA
 DBPR WEBSITE FOR LICENSURE. PLEASE CORRELATE. FAC
 61G1-16.001, 61G1-16.002 & FS 481.2055.
  
 7. SHTS P210 & P215 IN THE INSTALLATION OR REMOVAL OF
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. DISCONNECT ALL DRAINAGE A MAXIMUM OF 2 FEET
 FROM ACTIVE BUILDING DRAIN LINES. ALL PIPING CAPPED FOR
 DEMOLITION SHALL REMAIN UNCOVERED UNTIL INSPECTED AND
 APPROVED BY THE FIELD INSPECTOR. SECTION 704.5. PLEASE
 INDICATE ON THE DEMO SHEET THE LOCATION OF ALL
 CAPPED/ABANDONED PIPING.
  
 8. SHT P210 THE ABANDONED GREASE INTERCEPTOR SHALL BE
 PUMPED OUT, AND REMOVED, OR IT SHALL BE PUMPED OUT, THE
 BOTTOM SHALL BE SUITABLY OPENED OR RUPTURED SO AS TO
 PREVENT THE INTERCEPTOR FROM RETAINING WATER AND FILLED
 WITH CLEAN SAND OR OTHER SUITABLE MATERIAL, THE ACTIONS
 BEING TAKEN IN THE ORDER LISTED. ARTICLE III SECTION
 90-123, (CODE 1979 & 31-60).
  
 9. SHT P210 INDICATE WHAT DRAINS INTO FIXTURE P-16 &
 P30 F.S. SECTION 106.1.2.
  
 10. SHT P210 IDENTIFY THE FIXTURES CONNECTING TO DSP
 AND SUBMIT A DETAIL SHOWING HOW THEY ARE CONNECTED.
 SECTION, 106.1.2,
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  