Plan Review Notes
Plan Review Notes For Permit 08110178
Permit Number 08110178
Review Stop M
Sequence Number 1
Notes
Date Text
2008-11-22 16:06:04REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 THIS PROJECT REVIEWED FOR COMPLIANCE WITH THE FOLLOWING
 CODES:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLWING COMMENTS SHALL BE ADDRESSED PRIOR TO
 RESUBMISSION OF PLANS WITH PERMIT APPLICATION:
  
 1. THE DESIGN PROFESSIONAL MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE IN ACCORDANCE
 WITH FBCEB 301.5. PLEASE SHOW THIS ON PLANS WITH THE
 PROJECT INFORMATION.
  
 2. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND
 ALL SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE
 IN ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL PER FBCEB 609.1.
 PROVIDE VENTILATION CALCULATIONS FOR ALL RECONFIGURED
 SPACES IN ACCORDANCE WITH FBCM SECTION 403.
  
 3. PLANS CALL FOR NEW RTU AND EXHAUST FAN TO BE
 INSTALLED ON ROOF. NO INFORMATION COULD BE FOUND ON
 PLANS REGARDING WIND RESISTANCE. MECHANICAL APPLIANCES
 AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND PRESSURES ON THE
 EQUIPMENT AND THE SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH FBCB SECTION 1609 PER FBCM 301.13. PROVIDE
 ATTACHMENT DETAIL SHOWING ROOF CURBS TO BUILDING
 STRUCTURE AND RTU/EF TO ROOF CURB ATTACHMENTS. ALSO,
 PLEASE PROVIDE MANUFACTURER'S DATA SHOWING THESE
 APPLIANCES ARE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH THIS SECTION.
  
 4. PLANS CALL FOR DUCT SMOKE DETECTOR TO BE INSTALLED
 IN THE RETURN DUCT FOR RTU. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY AIR DUCT IN
 ACCORDANCE WITH FBCM 606.2.1.
  
 5. MECHANICAL FLOOR PLAN SHOWS FLEX DUCTS ATTACHED
 DIRECTLY TO FIRE DAMPERS. PROVIDE FD MANUFACTURER'S
 INSTALLATION INSTRUCTIONS SHOWING HOW FLEX DUCT IS TO
 BE ATTACHED TO THE DAMPERS. FIRE DAMPERS AND
 COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBCM 607.2.
  
 6. SHOW HOW DUCT ACCESS DOORS ARE TO BE INSTALLED AT
 THESE LOCATIONS. A SERVICE OPENING (DUCT ACCESS DOOR)
 SHALL BE PROVIDED IN AIR DUCTS ADJACENT TO EACH FIRE
 DAMPER, SMOKE DAMPER, AND DUCT SMOKE DETECTOR. THE
 OPENING SHALL BE LARGE ENOUGH TO PERMIT MAINTENANCE AND
 RESETTING OF THE DEVICE. SERVICE OPENINGS SHALL BE
 IDENTIFIED WITH LETTERS HAVING A MINIMUM HEIGHT OF 1/2
 INCH TO INDICATE THE LOCATION OF THE FIRE PROTECTION
 DEVICE(S) WITHIN THE DUCT IN ACCORDANCE WITH FBCM
 301.15 AND NFPA 90A-2002.
  
 7. EXHAUST/RETURN DETAIL CALLS FOR LINED GRILL CANS AND
 INSULATED FLEX. ALL EXHAUST DUCTS SHALL BE OF METAL
 (NON-LINED) AND SUCH CONSTRUCTION SHALL COMPLY WITH
 FBCM 501.4.
  
 NOTE: THE SUBMITTED METHOD A ENERGYCALCULATIONS WERE
 NOT REVIEWED FOR COMPLIANCE WITH THE MECHANICAL
 PROVISIONS OF THE FLORIDA ENERGY CODE (FBCB CHAPTER
 13). THIS PROJECT IS NOT NEW CONSTRUCTION, IS NOT A
 WHOLE BUILDING AND DOES NOT MEET THE DEFINITION OF A
 RENOVATION (SEE FBCB SECTION 13-202) AND THEREFORE ONLY
 COMPLIANCE WITH FBCB 13-101.6 NEEDS TO BE DEMONSTRATED.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH
 INFORMATION ON HOW EACH COMMENT WAS ADDRESSED AND WHERE
 THE RELEVANT INFOAMTION CAN BE FOUND. THIS WILL HELP TO
 FACILITATE A TIMELY REVIEW UPON RESUBMISSION.
  