2008-12-11 12:20:35***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION. ADD TO APPLICABLE CODES.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. ADD TO APPLICABLE CODES.
  
 3) PLEASE INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALSS AND CEILING IN TERMS OF CLASS
 A,B OR C.
  
 4) IN ADDITION TO SEPARATE PERMIT PROCESS, INDICATE THE
 FIRE SPRINKLER HEAD LAYOUT THAT MAY BE SHOWN ON THE
 RELECTED CEILING PLAN.
  
 5) DUCT SMOKE DETECTORS SHALL BE PROVIDED IN SUPPLY
 DUCT UNLESS UNITS ARE LARGE ENOUGH FOR BOTH SUPPLY AND
 RETURN. DUCT SMOKE DETECTORS SHALL BE TIED INTO THE
 FIRE ALARM SYSTEM IF APPLICABLE AND INITIATE A GENERAL
 FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 6) PLANS SEEM TO SUGGEST EXITING THROUGH STORAGE/WORK
 ROOMS. SPECIFIC AREAS WOULD PROVIDE AN AREA OF GREATER
 HAZARD. PLEASE PROVIDE INFORMATION THAT WOULD ALLOW
 THIS ARRANGEMENT.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756