| Plan Review Notes For Permit 08110178 |
| Permit Number |
08110178 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-11 12:20:35 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. ADD TO APPLICABLE CODES. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. ADD TO APPLICABLE CODES. | | | | | | 3) PLEASE INDICATE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALSS AND CEILING IN TERMS OF CLASS | | | A,B OR C. | | | | | | 4) IN ADDITION TO SEPARATE PERMIT PROCESS, INDICATE THE | | | FIRE SPRINKLER HEAD LAYOUT THAT MAY BE SHOWN ON THE | | | RELECTED CEILING PLAN. | | | | | | 5) DUCT SMOKE DETECTORS SHALL BE PROVIDED IN SUPPLY | | | DUCT UNLESS UNITS ARE LARGE ENOUGH FOR BOTH SUPPLY AND | | | RETURN. DUCT SMOKE DETECTORS SHALL BE TIED INTO THE | | | FIRE ALARM SYSTEM IF APPLICABLE AND INITIATE A GENERAL | | | FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 6) PLANS SEEM TO SUGGEST EXITING THROUGH STORAGE/WORK | | | ROOMS. SPECIFIC AREAS WOULD PROVIDE AN AREA OF GREATER | | | HAZARD. PLEASE PROVIDE INFORMATION THAT WOULD ALLOW | | | THIS ARRANGEMENT. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|