| 2008-12-01 17:48:27 | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW. PLEASE |
| | KNOW EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT AND |
| | PERMIT APPLICATION HAS NOT BEEN MADE THE REVIEW WILL |
| | STILL REMAIN IN A FAILED STATUS. VERIFICATION OF |
| | LICENSING AND SEVERAL OTHER ITEMS WILL TAKE PLACE ONCE |
| | PERMIT APPLICATION IS MADE. |
| | |
| | 2) NOTE: PLEASE SEE FLORIDA STATUTES 481.221 AS THE |
| | ONLY SEAL PERMITTED IS REQUIRED TO BE A RAISED |
| | IMPRESSION TYPE SEAL. SOME DOCUMENTS AND SHEETS |
| | SUBMITTED CONTAIN A *RUBBER-STAMPED* SEAL WHICH IS NOT |
| | PERMITTED. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE FOR ALL SHEETS. |
| | |
| | 3) NOTE: PLEASE SEE THE SEAL ON SHEETS WHICH IS AN |
| | IMPRESSION TYPE SEAL IS NO LONGER ACCEPTABLE IN THE |
| | STATE OF FLORIDA. PLEASE SEE FLORIDA ADMINISTRATIVE |
| | CODE 61G1-16.002 FOR CORRECT TYPE OF SEAL. THE INITIAL |
| | RULING OF A 2INCH SEAL WAS ADOPTED IN 1989. THIS HAS |
| | SINCE BEEN UPDATE HOWEVER HAS BEEN A REQUIREMENT FOR |
| | ALMOST 20YEARS. |
| | ** THIS IS REQUIRED WHETHER OR NOT THE COMMENT IS MADE |
| | BY ANY OTHER TRADES FOR ALL SHEETS. |
| | |
| | 4) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE |
| | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR THE |
| | ARCHITECTURAL FIRM. THIS IS REQUIRED ON TITLE BLOCKS |
| | PER FAC61G1-16.004 AND PER FLORIDA STATUTES 481.219 |
| | |
| | 5) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE |
| | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | ENGINEERING BUSINESS/FIRM PER FLORIDA ADMINISTRATIVE |
| | CODE (FAC 61G15-23.002) AND FS 471.023 |
| | |
| | 6) NOTE: PLEASE SEE THE TITLE BLOCKS ARE REQUIRED TO |
| | CONTAIN THE PRINTED NAME AND PRINTED LICENSE NUMBER OF |
| | THE DESIGNER. FAC 61G1-16.002, 61G15-23.002. |
| | ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 7) NOTE: PLEASE SEE THE RAISED SEAL WHICH DISPLAYS A |
| | LICENSE NUMBER. THE NUMBER AS PRINTED IN SEAL IS: |
| | AR90016025. THERE IS NO RECORD OF THIS LICENSE NUMBER |
| | ON THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION WEBSITE. THE NUMBER AS LISTED ABOVE WITHOUT |
| | THE *9* IS A RELEVANT NUMBER. |
| | PLEASE ADJUST SEAL. |
| | ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER |
| | OR NOT COMMENTS IS MADE BY OTHER TRADES REVIEWERS. |
| | |
| | 8) NOTE: PLEASE SEE THE PRINT OUT ATTACHED TO NOTES AS |
| | THE ADDRESS ON PLANS DOES NOT CORRELATE WITH THE TITLE |
| | BLOCKS. IN FACT THE STATE SITE LISTS AN ADDRESS OF |
| | 15380 KATA DR. ELM GROVE, WISCONSIN 53122. |
| | PLEASE CORRECT PLANS AND TITLE BLOCKS OR CONTACT THE |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION TO |
| | UPDATE INFORMATION. |
| | ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADE REVIEWERS. |
| | |
| | 9) NOTE: THE CODES RELEVANT TO PROJECT ARE REQUIRED TO |
| | MEET ADOPTED CODES UNDER FS 553.73. PLEASE SEE THAT THE |
| | PLANS ARE CURRENTLY LISTING CODES WHICH ARE NO LONGER |
| | ADOPTED IN THE STATE OF FLORIDA. SOME SUCH AS THE 2002 |
| | NATIONAL ELECTRICAL CODE AS SHOWN AS NOT BEEN IN EFFECT |
| | SINCE DECEMBER 2006. |
| | THE CODES FOR THIS REVIEWER ALONE SHOULD BE STATED AS |
| | FOLLOWS. |
| | |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70. ( NEC) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | * PLEASE NOTE, THE NFPA-72 MAY OR MAY NOT BE APPLICABLE |
| | TO THIS PROJECT. |
| | |
| | 10) NOTE: PLEASE SEE FBC 13-106.1.1. THE SUBMIT ENERGY |
| | CALCULATIONS ARE METHOD *A* WHICH IS FOR WHOLE BUILDING |
| | COMPLIANCE. PLEASE SEE DEFINITIONS IN SECTION 202 AS |
| | THIS IS NOT A WHOLE BUILDING OR NEW CONSTRUCTION. |
| | PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2,13-415.2.ABC.1.1, .1.2. |
| | |
| | 11) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND |
| | PLACE NOTES ON PLANS ACCORDINGLY. |
| | |
| | 12) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE LIGHTING |
| | CONTROLS NOTED AS *SPRING WOUND* TIMERS ARE NOT |
| | PERMITTED. |
| | MUST MEET ADA REQUIREMENTS. |
| | |
| | 13) NOTE: PLANS INDICATE ELECTRICAL PANELS IN WHAT |
| | WOULD BE A CLOSET FOR STORAGE OF SUPPLIES. |
| | PLEASE SEE 110.26,240.24D AND 408.17 AS ELECTRICAL |
| | EQUIPMENT ALONG WITH OVER CURRENT PROTECTION IS NOTED |
| | PERMITTED IN AREAS WHERE THERE IS STORAGE OF EASILY |
| | IGNITABLE MATERIALS OR COMBUSTIBLES. |
| | |
| | 14) NOTE: PLEASE INCLUDE LIGHTING CONTROLS AS REQUIRED |
| | PER 13-415.1.ABC.1.1,.1.2 AND .1.3. |
| | |
| | 15) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ALL |
| | MINIMUM LEVELS FOR DEVICES OF FIRE ALARM SYSTEM. |
| | PLEASE BE SURE ALL DEVICE HEIGHTS AND LEVELS ARE SHOWN. |
| | ** NOTE MINIMUM CANDELA LEVELS FOR STROBE DEVICES ARE |
| | 75CD |
| | |
| | 16) NOTE: PLEASE OBTAIN THE LATEST ELECTRICAL RISER FOR |
| | THIS SPACE. IT IS UNDERSTOOD THIS SAME TENANT HAS |
| | OBTAINED PERMITS FOR NEW GENERATOR AND ELECTRICAL |
| | EQUIPMENT WHICH IS NOT PART OF THE CURRENT SUBMITTED |
| | ELECTRICAL PLANS. |
| | 230,220,215,240 ETC |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS. |
| | |
| | 17) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS SUCH AS |
| | LIGHTING AT 125%. 215.3,230.42 ETC |
| | |
| | ** IT IS IMPORTANT TO KNOW AS THERE ARE SOME ITEMS NOT |
| | YET SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON |
| | THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | 18) NOTE: DOCUMENTATION HAS BEEN ROUTED TO THE |
| | ADDRESSING REVIEWER. THIS WILL BE ONE TENANT SPACE AND |
| | ADDRESS SHOULD BE LISTED UNDER A PRIME SUITE OR UNIT |
| | NUMBER. THE PLANS AND PLAN REVIEW APPLICATION IS |
| | PRESENTLY SUBMITTED AS THREE SEPARATE UNITS/SPACES. |
| | ONCE FINAL ADDRESS IS DETERMINED PLEASE ADJUST TITLE |
| | BLOCKS. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | FBC 106.5 |
| | |
| | 19) NOTE: PLEASE BE SURE ALL ELECTRICAL SERVICE |
| | EQUIPMENT ONCE REVISED IS LABELED ACCORDINGLY. TENANT |
| | DISCONNECTS AND MAINS NEED IDENTIFICATION IN ANY EVEN |
| | THE POWER NEEDS TO BE SHUT DOWN. |
| | 230.2E ECT. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |