2008-12-01 17:48:27 
 ** DENIED **
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW. PLEASE
 KNOW EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT AND
 PERMIT APPLICATION HAS NOT BEEN MADE THE REVIEW WILL
 STILL REMAIN IN A FAILED STATUS. VERIFICATION OF
 LICENSING AND SEVERAL OTHER ITEMS WILL TAKE PLACE ONCE
 PERMIT APPLICATION IS MADE.
  
 2) NOTE: PLEASE SEE FLORIDA STATUTES 481.221 AS THE
 ONLY SEAL PERMITTED IS REQUIRED TO BE A RAISED
 IMPRESSION TYPE SEAL. SOME DOCUMENTS AND SHEETS
 SUBMITTED CONTAIN A *RUBBER-STAMPED* SEAL WHICH IS NOT
 PERMITTED.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE FOR ALL SHEETS.
  
 3) NOTE: PLEASE SEE THE SEAL ON SHEETS WHICH IS AN
 IMPRESSION TYPE SEAL IS NO LONGER ACCEPTABLE IN THE
 STATE OF FLORIDA. PLEASE SEE FLORIDA ADMINISTRATIVE
 CODE 61G1-16.002 FOR CORRECT TYPE OF SEAL. THE INITIAL
 RULING OF A 2INCH SEAL WAS ADOPTED IN 1989. THIS HAS
 SINCE BEEN UPDATE HOWEVER HAS BEEN A REQUIREMENT FOR
 ALMOST 20YEARS.
 ** THIS IS REQUIRED WHETHER OR NOT THE COMMENT IS MADE
 BY ANY OTHER TRADES FOR ALL SHEETS.
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 ARCHITECTURAL FIRM. THIS IS REQUIRED ON TITLE BLOCKS
 PER FAC61G1-16.004 AND PER FLORIDA STATUTES 481.219
  
 5) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR
 ENGINEERING BUSINESS/FIRM PER FLORIDA ADMINISTRATIVE
 CODE (FAC 61G15-23.002) AND FS 471.023
  
 6) NOTE: PLEASE SEE THE TITLE BLOCKS ARE REQUIRED TO
 CONTAIN THE PRINTED NAME AND PRINTED LICENSE NUMBER OF
 THE DESIGNER. FAC 61G1-16.002, 61G15-23.002.
 ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 7) NOTE: PLEASE SEE THE RAISED SEAL WHICH DISPLAYS A
 LICENSE NUMBER. THE NUMBER AS PRINTED IN SEAL IS:
 AR90016025. THERE IS NO RECORD OF THIS LICENSE NUMBER
 ON THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WEBSITE. THE NUMBER AS LISTED ABOVE WITHOUT
 THE *9* IS A RELEVANT NUMBER.
 PLEASE ADJUST SEAL.
 ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER
 OR NOT COMMENTS IS MADE BY OTHER TRADES REVIEWERS.
  
 8) NOTE: PLEASE SEE THE PRINT OUT ATTACHED TO NOTES AS
 THE ADDRESS ON PLANS DOES NOT CORRELATE WITH THE TITLE
 BLOCKS. IN FACT THE STATE SITE LISTS AN ADDRESS OF
 15380 KATA DR. ELM GROVE, WISCONSIN 53122.
 PLEASE CORRECT PLANS AND TITLE BLOCKS OR CONTACT THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION TO
 UPDATE INFORMATION.
 ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADE REVIEWERS.
  
 9) NOTE: THE CODES RELEVANT TO PROJECT ARE REQUIRED TO
 MEET ADOPTED CODES UNDER FS 553.73. PLEASE SEE THAT THE
 PLANS ARE CURRENTLY LISTING CODES WHICH ARE NO LONGER
 ADOPTED IN THE STATE OF FLORIDA. SOME SUCH AS THE 2002
 NATIONAL ELECTRICAL CODE AS SHOWN AS NOT BEEN IN EFFECT
 SINCE DECEMBER 2006.
 THE CODES FOR THIS REVIEWER ALONE SHOULD BE STATED AS
 FOLLOWS.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70. ( NEC)
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE NOTE, THE NFPA-72 MAY OR MAY NOT BE APPLICABLE
 TO THIS PROJECT.
  
 10) NOTE: PLEASE SEE FBC 13-106.1.1. THE SUBMIT ENERGY
 CALCULATIONS ARE METHOD *A* WHICH IS FOR WHOLE BUILDING
 COMPLIANCE. PLEASE SEE DEFINITIONS IN SECTION 202 AS
 THIS IS NOT A WHOLE BUILDING OR NEW CONSTRUCTION.
 PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2,13-415.2.ABC.1.1, .1.2.
  
 11) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 12) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE LIGHTING
 CONTROLS NOTED AS *SPRING WOUND* TIMERS ARE NOT
 PERMITTED.
 MUST MEET ADA REQUIREMENTS.
  
 13) NOTE: PLANS INDICATE ELECTRICAL PANELS IN WHAT
 WOULD BE A CLOSET FOR STORAGE OF SUPPLIES.
 PLEASE SEE 110.26,240.24D AND 408.17 AS ELECTRICAL
 EQUIPMENT ALONG WITH OVER CURRENT PROTECTION IS NOTED
 PERMITTED IN AREAS WHERE THERE IS STORAGE OF EASILY
 IGNITABLE MATERIALS OR COMBUSTIBLES.
  
 14) NOTE: PLEASE INCLUDE LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.1,.1.2 AND .1.3.
  
 15) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ALL
 MINIMUM LEVELS FOR DEVICES OF FIRE ALARM SYSTEM.
 PLEASE BE SURE ALL DEVICE HEIGHTS AND LEVELS ARE SHOWN.
 ** NOTE MINIMUM CANDELA LEVELS FOR STROBE DEVICES ARE
 75CD
  
 16) NOTE: PLEASE OBTAIN THE LATEST ELECTRICAL RISER FOR
 THIS SPACE. IT IS UNDERSTOOD THIS SAME TENANT HAS
 OBTAINED PERMITS FOR NEW GENERATOR AND ELECTRICAL
 EQUIPMENT WHICH IS NOT PART OF THE CURRENT SUBMITTED
 ELECTRICAL PLANS.
 230,220,215,240 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 17) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS SUCH AS
 LIGHTING AT 125%. 215.3,230.42 ETC
  
 ** IT IS IMPORTANT TO KNOW AS THERE ARE SOME ITEMS NOT
 YET SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON
 THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 18) NOTE: DOCUMENTATION HAS BEEN ROUTED TO THE
 ADDRESSING REVIEWER. THIS WILL BE ONE TENANT SPACE AND
 ADDRESS SHOULD BE LISTED UNDER A PRIME SUITE OR UNIT
 NUMBER. THE PLANS AND PLAN REVIEW APPLICATION IS
 PRESENTLY SUBMITTED AS THREE SEPARATE UNITS/SPACES.
 ONCE FINAL ADDRESS IS DETERMINED PLEASE ADJUST TITLE
 BLOCKS.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.5
  
 19) NOTE: PLEASE BE SURE ALL ELECTRICAL SERVICE
 EQUIPMENT ONCE REVISED IS LABELED ACCORDINGLY. TENANT
 DISCONNECTS AND MAINS NEED IDENTIFICATION IN ANY EVEN
 THE POWER NEEDS TO BE SHUT DOWN.
 230.2E ECT.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  