| Plan Review Notes For Permit 08110134 |
| Permit Number |
08110134 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-08 09:54:56 | | | | | | | DENIED | | | | | | 1) PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL | | | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 & | | | 2007AMENDMENTS PER 106.1.1 FBC* | | | | | | 2) IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING | | | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF | | | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND | | | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE | | | DRAWINGS. | | | | | | 3) PROVIDE A SCOPE OF WORK ON THE DRAWING. IS THIS ONE | | | REPAIR AND WINDOW?, WAS THIS A CHANGE IN OPENING SIZE?, | | | IS A NEW WINDOW BEING INSTALLED? IF SO PRODUCT | | | APPROVALS THAT ARE REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD ARE REQUIRED. | | | | | | 4) DRAWING SHOWS NEW REINFORCED FILL CELL ON ONLY ONE | | | SIDE IS THE OTHER SIDE OF WINDOW OPENING AN EXISTING | | | FILLED BLOCK CELL. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|