Plan Review Notes
Plan Review Notes For Permit 08110134
Permit Number 08110134
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-08 09:54:56 
  
 DENIED
  
 1) PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 &
 2007AMENDMENTS PER 106.1.1 FBC*
  
 2) IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS.
  
 3) PROVIDE A SCOPE OF WORK ON THE DRAWING. IS THIS ONE
 REPAIR AND WINDOW?, WAS THIS A CHANGE IN OPENING SIZE?,
 IS A NEW WINDOW BEING INSTALLED? IF SO PRODUCT
 APPROVALS THAT ARE REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD ARE REQUIRED.
  
 4) DRAWING SHOWS NEW REINFORCED FILL CELL ON ONLY ONE
 SIDE IS THE OTHER SIDE OF WINDOW OPENING AN EXISTING
 FILLED BLOCK CELL.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  