| 2008-11-17 11:39:15 | |
| | |
| | |
| | ** FAILED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR * PLAN |
| | REVIEW* AND HAVE NOT BEEN SUBMITTED FOR PERMIT |
| | APPLICATION. |
| | AS THE PLANS SUBMITTED ARE FOR REVIEW OF SLAB ONLY |
| | PLEASE BE AWARE OF COMMENTS BELOW AND FROM OTHER |
| | TRADES. THE FUTURE WILL NEED PLANS SHOWING ALL |
| | ELECTRICAL AND LIGHTING AS NOTED BELOW. |
| | |
| | 2) NOTE: PLEASE SUBMIT A PLANS SHOWING THE LIFE SAFETY |
| | REQUIREMENTS FOR LIGHTING FOR EGRESS UNDER NORMAL AND |
| | EMERGENCY CONDITIONS. PLEASE SEE NFPA-101 2003 , 7.8 |
| | AND 7.9. |
| | PLEASE SEE NEC 700.12F FOR CIRCUITING. |
| | ** |
| | |
| | 3) NOTE: PLEASE SUBMIT A DETAIL FOR GROUNDING ELECTRODE |
| | SYSTEM AS REQUIRED PER 250.50 FOR ELECTRICAL SERVICE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |