| Plan Review Notes For Permit 08110110 |
| Permit Number |
08110110 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-01-27 09:15:27 | 1) IT APPEARS THAT RESPONSES HAVE BEEN PROVIDED TO | | | PREVIOUS COMMENTS MADE BY THE FIRE RESCUE DEPARTMENT. | | | | | | 2) NOTE # 3 BELOW DOOR SCHEDULE INDICATES ON PAGE A-1 | | | THAT "EXISTING GATES DESIGNATED TO BE PART OF AN EGRESS | | | SYSTEM SHALL REMAIN UNLOCKED OR AUTOMATICALLY UNLOCK IN | | | CASE OF FIRE DURING HOURS OF OPERATION". HOW DOES THIS | | | AUTOMATIC UNLOCKING OCCUR. | | | | | | 3) ON PAGE A-3 IT HAS BEEN DECLARED THAT OCCUPANT | | | ACTIVITIES WILL INLCUDE "ADULT EDUCATION AND RELIGIOUS | | | ACCESSORY USE". SOME INFORMATION SUGGESTS THAT THESE | | | FACILITIES MAY BE USED FOR AN ADULT DAY CARE AND IS NOT | | | DECLEARED ON THE PLANS. THIS INFORMATION IF TRUE NEEDS | | | TO BE DECLARED ON THE PLANS. THE MINIMUM BUILDING AND | | | FIRE CODE REQURIEMENTS SHALL BE MET FOR THE SPECIFIC | | | OCCUPANCY TYPE AND USE. THE BUILDING AND ELECTRICAL | | | PLAN REVIEWERS HAVE BOT DENIED THESE REVISED PLANS. | | | PLEASE REVISE PLANS ACCORDINGLY AND ENSURE THAT ALL | | | INFORMATION HAS BEEN PROVIDED. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|