| Date |
Text |
| 2008-12-02 16:56:07 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 EXISTING BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1, ALL SHEETS SEALED BY THE ARCHITECT OF RECORD ARE |
| | REQUIRED TO HAVE THE SIGNATURE OF THE DESIGN |
| | PROFESSIONAL. IT APPEARS THAT INITIALS HAVE BEEN USED |
| | IN PLACE OF THE SIGNATURE. IF THE INITIALS ARE INDEED |
| | THE LEGAL SIGNATURE OF THE DESIGN PROFESSIONAL, THEN A |
| | SIGNED, SEALED, NOTORIZED LETTER INDICATING THE LEGAL |
| | SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR OUR |
| | RECORDS. FAC 61G1-16.003, 61G1-16.004(5) & FS 481.2055. |
| | |
| | 2. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE |
| | WORK INDICATED CAN BE VERIFIED. SECTION 106.1.2. |
| | |
| | 3. SHT A-1 SHOW THE ROOM NUMBERS THAT CORRESPOND TO THE |
| | ROOMS INDICATED ON THE APPLICATION FOR PERMIT. SECTIONS |
| | 106.1.1 & 106.1.2. |
| | |
| | 4. SHT A-1 TOILET ROOMS SHOW IMAGES OF W/C'S IN THE |
| | WOMEN'S AND MEN'S TOILET ROOMS AND AN IMAGE OF A LAV IN |
| | THE MEN'S TOILET SUPERIMPOSED OVER THE W/C AND LAV. ARE |
| | THE FIXTURES BEING DELETED OR MOVED FROM THERE ORIGINAL |
| | LOCATION? PLEASE CLARIFY. IF FIXTURES ARE DELETED THEN |
| | CALCULATION FOR MINIMUM FACILITIES PER TABLES 1004.1.2 |
| | & 403.1 ARE REQUIRED TO INDICATE COMPLIANCE WITH |
| | REQUIRED FIXTURES. SECTION 106.1.1. ARE THERE REQUIRED |
| | DRINKING FOUNTAINS? |
| | |
| | 5. SHT A-1 INDICATES CODE REQUIREMENTS WITH 2006 |
| | REVISIONS. CODE SHALL ALSO INCLUDE THE 2007 REVISIONS |
| | AS WELL AS THE 2005 REVISIONS. SECTION 106.1.1. |
| | |
| | 6. INDICATE THE LEVEL OF ALTERATION AS REQUIRE IN |
| | SECTION 301 OF THE EXISTING BUILDING CODE. |
| | |
| | 7. SHT A-1 INDICATES 4 ABANDONED GAS BASE BOARD HEATERS |
| | AND A NEW 30 GALLON GAS WATER HEATER. A SEPARATE GAS |
| | PERMIT IS REQUIRED THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | 8. SHT P-1 THE SANITARY RISER DIAGRAM SHOWS AN EXISTING |
| | W/C & LAV BY THE CLASSROOM SINK THAT IS NOT SHOWN ON |
| | THE FLOOR PLAN. PLEASE CLARIFY. SHOW THE EXISTING |
| | TOILET ROOM ON THE FLOOR PLAN. SECTIONS 106.1.1, |
| | 106.1.2 & 701.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |