| 2008-11-25 11:28:00 | |
| | |
| | |
| | |
| | |
| | ** FAILED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: A CALLED WAS PLACED TO RON GILMAN WHO IS THE |
| | ELECTRICAL ENGINEER OF RECORD FOR PROJECT. THE NEW |
| | ELECTRICAL PANEL AND EXISTING DISCONNECTS NEED TO BE |
| | VERIFIED IF THEY CONTAIN A LOCKING TYPE COVER FOR THE |
| | OCCUPANCY ALONG WITH A LOCKING COVER FOR THE |
| | DISCONNECT. |
| | THERE MAY BE SOME OTHER OPTIONS SUCH AS A SHORT WALL |
| | WITH A LOCKING DOOR OF SOME TYPE GIVING THE CLEARANCE |
| | REQUIREMENTS PER 110.26, 240.24 |
| | ENGINEER WAS GOING TO LOOK INTO OPTIONS AND CONTACT THE |
| | ARCHITECT. |
| | |
| | 2) NOTE: NEED EQUIPMENT GROUNDING CONDUCTOR FROM |
| | DISCONNECT TO NEW PANEL. |
| | 250.110,250.122 |
| | |
| | 3) NOTE: PLEASE SEE 422.30, 422.31 AS THE WATER HEATER |
| | REQUIRES A DISCONNECT. THE PLANS SHOW A RECEPTACLE |
| | WHICH IS NOT PERMITTED. |
| | |
| | 4) NOTE: OCCUPANCY FOR INTENDED USE WILL NEED TO BE ON |
| | PLANS PER FBC CHAPTER 3, 303.1 |
| | |
| | 5) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS WHICH CALL |
| | FOR TWO NEW ELECTRICAL PANELS. PLEASE COORDINATE. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |