| 2008-11-26 13:12:45 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PROVIDE A DEMO PLAN WHICH SHOULD INCLUDE EXISTING |
| | FLOOR PLAN. SCOPE IS NOT CLEAR. IT IS NOT CLEAR WHICH |
| | WALLS ARE EXISTING, WHICH ARE NEW. |
| | |
| | 2. PLEASE NOTE THAT THE FLOOR PLAN SHOWN ON A1 DOES NOT |
| | IDENTIFY DOORS, ROOMS, OR CORRIDORS. FOR INSTANCE, |
| | THERE ARE FIVE DIFFERENT ROOMS LABELED "EXISTING |
| | CLASSROOM". THERE ARE MANY DOORS BUT THEY ARE NOT |
| | LABELED, AND AS THE ROOMS AND CORRIDORS ARE NOT LABELED |
| | IT IS DIFFICULT FOR ME TO IDENTIFY WHICH DOOR, ROOM, OR |
| | CORRIDOR IS REFERRED TO IN THE COMMENT. ROOM |
| | DESIGNATION NUMBERS, OR A DOOR SCHEDULE, WOULD BE |
| | HELPFUL. |
| | |
| | 3. PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, BUILDING |
| | HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY |
| | CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | 4. DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. |
| | |
| | 5. GOVERNING CODE SHOULD INCLUDE 2007 |
| | REVISIONS/SUPPLEMENTS (EFFECTIVE JULY 1, 2007). |
| | |
| | 6. SHOW CORRIDOR WIDTHS. FBC11-4.8.6, FBC10. |
| | |
| | 7. DECLARE SQUARE FOOT AREA AND OCCUPANT LOAD FOR EACH |
| | ROOM. FBC10. |
| | |
| | 8. A DOOR IS SHOWN AS SWINGING AGAINST THE DIRECTION OF |
| | TRAVEL. SEE COMMENT 7; CLARIFY REQUIREMENTS FBC1008.1. |
| | 9. A 1" SLOPE IS SHOWN IN THE CORRIDOR. SPECIFY THE |
| | WIDTH, FBC10, FBC11. |
| | |
| | 10. A 4" ELEVATION CHANGE IS SHOWN AT A DOOR. SEE |
| | FBC1003.5.2, FBC1104.3.8. |
| | |
| | 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE |
| | REQUIRED WIDTH. PROVIDE DIMESIONS TO SHOW COMPLIANCE. |
| | |
| | 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE |
| | 11-25, PULL SIDE. |
| | |
| | 13. A2, DETAIL LABELED AS "GUARDRAIL". NOTE THAT A |
| | GUARDRAIL IS REQUIRED TO BE 42", BUT THIS IS SHOWN AS |
| | 36". IS A GUARDRAIL REQUIRED? FBC1012.1. IS THIS A |
| | HANDRAIL RATHER THAN A GUARDRAIL? |
| | |
| | 14. A TYPICAL INTERIOR PARTITION DETAIL WAS PROVIDED. |
| | HOWEVER, IT IS NOT CLEAR WHAT THIS IS FOR; EXISTING OR |
| | PROPOSED? ALSO (WALL LEGEND) NOTE THAT THE GRAPHIC FOR |
| | THE BLOCK WALL DOES NOT MATCH THE GRAPHIC USED FOR THE |
| | EXTERIOR WALL, AND THE GRAPHIC FOR THE FRAME WALL DOES |
| | NOT APPEAR ON THE FLOOR PLAN. SEE OTHER COMMENTS |
| | REGARDING SCOPE OF WORK. |
| | |
| | 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE |
| | PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIED |
| | FBC TABLE 1016.1. |
| | |
| | 16. WHAT DO THE DASHED LINES REPRESENT? THEY APPEAR IN |
| | TWO DIFFERENT EXISTING CLASSROOMS. |
| | |
| | 17. A3, LIFE SAFETY PLAN, THE PATH OF TRAVEL SHOULD BE |
| | MEASURED ALONG THE PATH OF ANTICIPATED TRAVEL. IT IS |
| | SHOWN GOING THROUGH THE CENTER OF THE ROOM, WHERE A |
| | CLASSROOM WOULD NORMALLY HAVE CHAIRS AND DESKS. PATH OF |
| | TRAVEL SHOULD BE SHOWN ALONG THE PERIMETER OF THE ROOM. |
| | |
| | 18. PROVIDE MORE INFORMATION REGARDING THE EXIT |
| | DISCHARGE. THE LIFE SAFETY PLAN MEASURES TO THE RAMP |
| | BASE. IS THIS THE OUTSIDE? A DOOR IS SHOWN ADJACENT TO |
| | THE RAMP IN THE HALLWAY. COVERED WALKWAYS SHOULD BE |
| | INCLUDED IN PATH OF TRAVEL. FBC1002. PLAN SHOULD SHOW |
| | WHERE THE OCCUPANT WILL LEAVE THE BUILDING (INCLUDING |
| | COVERED WALKWAYS). |
| | |
| | 20. DOES THE BUILDING HAVE A FIRE ALARM? SEE |
| | FBC11-4.28. NOTE THAT A VISUAL SIGNAL IS REQUIRED IN |
| | THE RESTROOMS; NONE SHOWN. |
| | |
| | 21. THE PROPOSED CHANGE OF DOOR SWING APPEARS TO |
| | INTERFERE WITH THE DOOR SWING OF THE ADJACENT DOOR, |
| | FBC1008. PLEASE REVISE. |
| | |
| | |
| | |