| Plan Review Notes For Permit 08110107 |
| Permit Number |
08110107 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-07 14:18:25 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PER FLORIDA STATUTE 471.003 AN ENGINEER MUST DESIGN | | | THIS SERVICE. THE CONTRACTOR OF RECORD MAY BE THE | | | DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES | | | ARE APPLICABLE. IN THIS CASE ENGINEERING IS REQUIRED | | | BECAUSE THE SERVICE VOLTAGE IS OVER 240 VOLTS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|