2008-11-06 16:24:40GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS. PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED GAS ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 WITH NO CORRESPONDING LENGTHS BEING INDICATED AND
 COMPLY ON THE RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED GAS ISOMETRIC ONLY INDICATES THE
 PIPING MATERIAL AND SIZE OF THE UNDERGROUND GAS PIPE.
 WHAT ARE THE PIPE SIZES AND MATERIAL TYPE OF THE
 PROPOSED ABOVEGROUND GAS PIPE?
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THE SUBMITTED GAS ISOMETRIC LONGEST RUN
 INDICATES 160', HOWEVER AS WAS STATED IN COMMENT #1 NOT
 ALL CUT SECTIONS HAVE CORRESPONDING LENGTHS BEING
 INDICATED. PLEASE REFERENCE COMMENT #1 AND CORRECT AND
 CORRELATE LONGEST LENGTH ON THE RESUBMITTAL.
  
 4. PLEASE KNOW THAT MP REGULATORS (2 PSI TO 0.5 PSI)
 SHALL BE REQUIRED FOR THE GAS SYSTEM AND NEED TO BE
 CLEARLY INDICATED ON THE RESUBMITTED GAS ISOMETRIC. PER
 FBC-2004 FUEL GAS SECTION 410.1 PRESSURE REGULATORS.
  
 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR AND CLEARLY
 INDICATED ON THE RESUBMITTAL.
  
 6. SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR THE MP
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. THE
 MANUFACTURE SHEETS SHALL CLEARLY INDICATE THE MP
 REGULATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 SUCH AS CSA, AGA OR UL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  