| Notes |
| Date |
Text |
| 2008-11-19 10:56:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. SPECIFY ANCHOR LENGTH AND SPACING, MINIMUM EDGE | | | DISTANCE, FBC R301, TO SHOW HOW THE PROPOSED GENERATOR | | | WILL RESIST OVERTURNING, SLIDING, AND UPLIFT. | | | CALCULATIONS, SPEC SHEETS FOR THE ANCHORS, MAY BE | | | REQUIRED. | | | | | | 2. DECLARE WIND DESIGN CRITERIA, FBC R301. | | | | | | 3. THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN IS | | | TO SIGN THE PLANS, FBC*106. | | | | | | | | | | | | |
|