2008-12-09 16:57:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT 1 DEMO SHEET, DEMOLITION NOTES STATE CAP ALL
 REMOVED PLUMBING FLUSH WITH THE FLOOR AND BEHIND
 GYPBORD AT CHASE PARTITIONS. PER SECTION 704.5 IN THE
 REMOVAL OF ANY DRAINAGE PIPING, DEAD ENDS ARE
 PROHIBITED. ALL SANITARY DRAINAGE PIPING SHALL BE
 CAPPED OFF WITHIN TWO FEET OF AN ACTIVE BUILDING DRAIN.
 PLEASE INDICATE ON THE PLANS WHERE THE PIPING WILL BE
 CAPPED OFF.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  