2009-03-13 16:25:11** PROVISO/REDLINED **
  
 1) NOTE: ALTHOUGH THE LOAD FOR THE LAUNDRY CIRCUIT WAS
 REVISED TO 1.5, THE LOAD CALCULATIONS WERE NOT UPDATED.
 PLEASE ALSO SEE THE WASHER CIRCUIT LOAD IS A LAUNDRY
 CIRCUIT. 1.5 REQUIRED.
 EVEN AS THIS ADDITIONAL LOAD WILL NOT AFFECT THE OVER
 ALL SIZE OF THE SERVICE THE CALCULATIONS DO NEED TO BE
 UPDATED.
 220, 210.11C2, 220.52.
  
 2) NOTE: PLEASE SEE THE SECOND SMALL APPLIANCE CIRCUIT
 WHICH DOES NOT INDICATE ANY BREAKER. THE REQUIRED 20AMP
 BREAKER
  
 ** PLEASE REVISE ALONG WITH ANY OTHER REVISIONS BEFORE
 ROUGH ELECTRICAL INSPECTION. THE PLANS WILL NEED TO BE
 SUBMITTED, REVISED AND ON THE JOBSITE BEFORE SCHEDULING
 AN INSPECTION.
  