| Date |
Text |
| 2009-02-12 11:04:19 | ** DENIED 2ND REVIEW ** |
| | |
| | ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF |
| | ADDRESSING FROM THE PREVIOUS REVIEWS. |
| | |
| | 1) NOTE: PLEASE COORDINATE CIRCUITING ON PLANS WITH |
| | THAT OF THE PANEL SCHEDULE SUBMITTED. THE FOLLOWING ARE |
| | SOME EXAMPLES. |
| | |
| | FOR EXAMPLE: PLEASE SEE THE CIRCUIT L28/30 ON PLANS FOR |
| | RANGE/COOK TOP WHICH IS NOTED AS KITCHEN AND FAMILY |
| | ROOM LTS AS WELL AS DINING ROOM RECEPTACLES. |
| | |
| | FOR EXAMPLE: PLEASE SEE CIRCUIT L-25 ON PLANS UNDER |
| | STAIRS WHICH NOTES ON PANEL SCHEDULE AS BEING THE |
| | RANGE/COOK-TOP. |
| | |
| | FOR EXAMPLE: SMALL APPLIANCE KITCHEN COUNTER |
| | RECEPTACLES MAY NOT FEED OTHER AREAS AS STATED IN |
| | 210.52B1. SEE OTHER AREAS IN THIS SECTION WHICH ARE |
| | PERMITTED HOWEVER FAMILY ROOM IS NOT ONE OF THEM. |
| | |
| | ** THESE ARE SOME EXAMPLES. |
| | NEC 408.4 |
| | FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION, CLARITY |
| | OF RECORD PLANS. |
| | PREVIOUS REVIEW |
| | |
| | 2) NOTE: PLEASE SEE 210.11C2, 220.52 FOR REQUIRED LOAD |
| | OF LAUNDRY CIRCUIT. THIS IS STILL TOO LOW. |
| | PREVIOUS REVIEW. |
| | |
| | 3) NOTE: PLEASE SEE 210.11C1, 220.52A FOR THE ONE O OR |
| | MORE OF THE SMALL APPLIANCE CIRCUITS AND THE LIKE SUCH |
| | AS DINING ROOM PER 210.52B1. |
| | ( MINIMUM VA PER EACH OF THESE IS 1500VA) |
| | ONLY SHOWS LOAD FOR TWO ON THE LOAD CALCULATIONS. |
| | PREVIOUS REVIEW. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-606.1.ABC.1.2.4 AS THE TYPE |
| | OF RECESSED CAN NOW NOTED ON PLANS IS NOT THE TYPE |
| | REQUIRED. |
| | PLEASE SEE THE SECTION OF THE CODE NOTED AND PLEASE SEE |
| | THE MANUFACTURES SPECS/CUT SHEETS FOR THE TYPE OF |
| | FIXTURE AS NOTED ON PLANS. THE PLANS STATE ICIT WHICH |
| | IS NOT AN AIR TIGHT CAN. |
| | |
| | 5) NOTE: PLEASE SHOW THE LOCATION OF THE NEW SERVICE |
| | MAIN. 230.70,230.2,240.24,110.26 ETC |
| | PLANS SHOW THE METER AND THE SUB PANELS BUT NOT THE |
| | MAIN DISCONNECT. |
| | |
| | 6) NOTE: PLEASE SEE 110.26 FOR REQUIRED CLEARANCES FOR |
| | THE A/C DISCONNECTS. |
| | THESE ARE CURRENTLY SHOWN BEHIND THE UNITS ON PLANS. IF |
| | THIS HAD BEEN THE ONLY ITEM IT WOULD HAVE BEEN REDLINED |
| | ON PLANS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |