2009-02-12 11:04:19** DENIED 2ND REVIEW **
  
 ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF
 ADDRESSING FROM THE PREVIOUS REVIEWS.
  
 1) NOTE: PLEASE COORDINATE CIRCUITING ON PLANS WITH
 THAT OF THE PANEL SCHEDULE SUBMITTED. THE FOLLOWING ARE
 SOME EXAMPLES.
  
 FOR EXAMPLE: PLEASE SEE THE CIRCUIT L28/30 ON PLANS FOR
 RANGE/COOK TOP WHICH IS NOTED AS KITCHEN AND FAMILY
 ROOM LTS AS WELL AS DINING ROOM RECEPTACLES.
  
 FOR EXAMPLE: PLEASE SEE CIRCUIT L-25 ON PLANS UNDER
 STAIRS WHICH NOTES ON PANEL SCHEDULE AS BEING THE
 RANGE/COOK-TOP.
  
 FOR EXAMPLE: SMALL APPLIANCE KITCHEN COUNTER
 RECEPTACLES MAY NOT FEED OTHER AREAS AS STATED IN
 210.52B1. SEE OTHER AREAS IN THIS SECTION WHICH ARE
 PERMITTED HOWEVER FAMILY ROOM IS NOT ONE OF THEM.
  
 ** THESE ARE SOME EXAMPLES.
 NEC 408.4
 FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION, CLARITY
 OF RECORD PLANS.
 PREVIOUS REVIEW
  
 2) NOTE: PLEASE SEE 210.11C2, 220.52 FOR REQUIRED LOAD
 OF LAUNDRY CIRCUIT. THIS IS STILL TOO LOW.
 PREVIOUS REVIEW.
  
 3) NOTE: PLEASE SEE 210.11C1, 220.52A FOR THE ONE O OR
 MORE OF THE SMALL APPLIANCE CIRCUITS AND THE LIKE SUCH
 AS DINING ROOM PER 210.52B1.
 ( MINIMUM VA PER EACH OF THESE IS 1500VA)
 ONLY SHOWS LOAD FOR TWO ON THE LOAD CALCULATIONS.
 PREVIOUS REVIEW.
  
 4) NOTE: PLEASE SEE FBC 13-606.1.ABC.1.2.4 AS THE TYPE
 OF RECESSED CAN NOW NOTED ON PLANS IS NOT THE TYPE
 REQUIRED.
 PLEASE SEE THE SECTION OF THE CODE NOTED AND PLEASE SEE
 THE MANUFACTURES SPECS/CUT SHEETS FOR THE TYPE OF
 FIXTURE AS NOTED ON PLANS. THE PLANS STATE ICIT WHICH
 IS NOT AN AIR TIGHT CAN.
  
 5) NOTE: PLEASE SHOW THE LOCATION OF THE NEW SERVICE
 MAIN. 230.70,230.2,240.24,110.26 ETC
 PLANS SHOW THE METER AND THE SUB PANELS BUT NOT THE
 MAIN DISCONNECT.
  
 6) NOTE: PLEASE SEE 110.26 FOR REQUIRED CLEARANCES FOR
 THE A/C DISCONNECTS.
 THESE ARE CURRENTLY SHOWN BEHIND THE UNITS ON PLANS. IF
 THIS HAD BEEN THE ONLY ITEM IT WOULD HAVE BEEN REDLINED
 ON PLANS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717