| 2008-11-17 13:54:45 | ** FAILED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE |
| | LISTED ON ELECTRICAL PLANS FOR DESIGN. |
| | 2005 NFPA-70 ( NEC) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** PLANS INDICATE PALM BEACH COUNTY WHEN THE ACTUAL |
| | APPLIED LOCATION IS IN THE CITY OF WEST PALM BEACH |
| | |
| | 2) NOTE: PLEASE INDICATE THE AIC RATING OF NEW SERVICE |
| | EQUIPMENT. 110.9 |
| | |
| | 3) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTOR |
| | AS REQUIRED PER 250.110,250.6,250.24 IS MISSING. PLEASE |
| | SEE 250.122 FOR SIZING. |
| | |
| | 4) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE |
| | SYSTEM. PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS A |
| | REQUIRED ATTACHMENT. PLEASE SEE THE RISER INDICATE |
| | 3-#4. WHY IS THERE THREE OF THESE NUMBER FOUR |
| | CONDUCTORS? IS THIS A MISPRINT? |
| | PLEASE REVISE. |
| | PLEASE INCLUDE METALLIC COLD WATER PIPE. |
| | |
| | 5) NOTE: PLEASE SEE PLANS AS THE SMOKE DETECTION |
| | DEVICES ARE SHOWN AS *SD*. THERE IS NO SYMBOL LEGEND |
| | HOWEVER AS A STANDARD OF INDUSTRY THESE WOULD BE SMOKE |
| | DETECTORS. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V AND |
| | WOULD DETECT AND SOUND AN ALARM. IF THESE ARE IN FACT |
| | SMOKE DETECTORS PLEASE INCLUDE THE ENTIRE SYSTEM. IF |
| | THESE ARE IN FACT SMOKE ALARMS PLEASE ADJUST PLANS. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 6) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING |
| | IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS |
| | TO SHOW MEETING THE CURRENT CODE FOR SMOKE |
| | DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE |
| | EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES |
| | INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A |
| | MULTI-LEVEL BUILDING. |
| | PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON |
| | THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN |
| | NFPA-72 OR CALL TO GO OVER. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | AS NOTED IN NOTE #5 ABOVE PLEASE COORDINATE. |
| | |
| | 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 FOR |
| | REQUIRED LOADS TO BE FIGURED FOR SMALL APPLIANCE AND |
| | DINING ROOM RECEPTACLES, BREAKFAST AREAS AND AREAS OF |
| | THE LIKE. THE LOAD SHOWN AS PORTABLE APPLIANCES IS TOO |
| | LOW. |
| | |
| | 8) NOTE: PLEASE SEE 210.11C2, 220.52 AS THE |
| | WASHER/LAUNDRY CIRCUIT IS ALSO REQUIRED TO BE FIGURED |
| | FOR A MINIMUM VA LOAD. THE VA LOAD AS SHOWN ON THE |
| | CALCULATIONS IS TOO LOW. |
| | |
| | 9) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. THIS HAS |
| | BEEN REVISED FROM THE 2002 NEC AS STORAGE TYPE WATER |
| | HEATERS ARE NOW CONSIDERED CONTINUOUS LOADS. PLEASE SEE |
| | DEFINITIONS IN NEC ARTICLE 100 AND LOADS UNDER |
| | 2154.3,230.42, 220.40 ETC |
| | ALL CONTINUOUS LOADS ARE REQUIRED TO BE FIGURED AT |
| | 125%. THIS WAS A CHANGE TO THE 2005 CODE. |
| | |
| | 10) NOTE: PLEASE SEE THE PLANS SEEM TO SHOW A |
| | RECEPTACLE FOR ONE OF THE WATER HEATERS. PLEASE SEE |
| | 4220.30,422.31 AS THIS IS REQUIRED TO BE A DISCONNECT. |
| | MAY NOT USE A CORD AND PLUG FOR THE DISCONNECTING MEANS |
| | FOR THIS LOAD. |
| | |
| | 11) NOTE: PLEASE SEE 440.11 AS THE A/C EQUIPMENT IS |
| | MISSING REQUIRED DISCONNECTS. THIS COMMENT IS FOR ALL |
| | EQUIPMENT. NOT ALL IS SHOWN. |
| | |
| | 12) NOTE: PLEASE SEE 210.63 FOR MISSING REQUIRED |
| | SERVICE RECEPTACLE(S). |
| | PLEASE SEE 210.8A3 FOR OUTDOOR RECEPTACLES WHICH ARE |
| | REQUIRED TO BE GFI/ GFI PROTECTED. |
| | |
| | 13) NOTE: PLEASE SEE 210.52C1-5. THERE ARE A COUPLE OF |
| | RECEPTACLES MISSING ALONG COUNTER SPACES AS SHOWN. |
| | |
| | 14) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| | KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI. AT THIS |
| | TIME ONLY RECEPTACLES WITHIN 6FT OF THE SINK ARE SHOWN |
| | AS GFI PROTECTED. THIS CHANGED IN THE 1993 NEC. |
| | |
| | 15) NOTE: PLEASE LIST THE REQUIRED AFCI ( ARC FAULT) |
| | PROTECTED CIRCUITS PER 210.12. |
| | PLEASE KEEP IN MIND THAT ALL OUTLETS INCLUDING |
| | RECEPTACLES, SMOKE ALARM DEVICES, FANS, LIGHTS ETC ARE |
| | REQUIRED TO BE PROTECTED. |
| | |
| | 16) NOTE: PLEASE SEE 424.3B FOR REQUIRED OVER CURRENT |
| | PROTECTION OF THE HEAT IN THE AIR HANDLING UNITS. |
| | REQUIRES 125% MINIMUM. |
| | |
| | 17) NOTE: PLEASE SEE 210.52 FOR SOME MISSING |
| | RECEPTACLES. PLEASE SEE ONE SET OF PLANS HAS SOME |
| | REDLINES HOWEVER THESE ARE NOT ALL. PLEASE BE AWARE OF |
| | THE 2FT, 6FT, 12 FT RULE. SEE PLANS, RECEPTACLES |
| | REQUIRED WITHIN 6FT OF DOOR. |
| | |
| | 18) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR REQUIRED |
| | DEDICATED BATH CIRCUIT(S). MUST BE 20AMP AND #12. |
| | |
| | 19) NOTE: PLEASE SEE THE REFRIGERATOR IS SHOWN AS #8 |
| | CONDUCTOR ON A 20AMP BREAKER. THIS MUST BE A MISPRINT. |
| | PLEASE ADJUST. |
| | PLEASE SEE OTHER CONDUCTOR SIZES ON THE SCHEDULE IF |
| | THESE ARE SHOWN THEN THE ELECTRICAL CONTRACTOR WILL BE |
| | REQUIRED TO INSTALL PER PLANS OR PLANS WILL BE REQUIRED |
| | TO BE REVISED. |
| | 110.3. |
| | FBC 106.1.1, FOR CLARITY, COORDINATION. |
| | |
| | 20) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE IS |
| | REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| | THEY FEED. PLEASE SEE THE FOLLOWING TEXT WHICH IS |
| | EXTRACTED DIRECTLY FROM THE 2005 NEC. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.1.1,106.3.5.4,106.5 |
| | |
| | 21) NOTE: THIS COMMENT IS BASED ON UNKNOWN LIGHTING IN |
| | THE REMAINDER OF THE DWELLING. PLEASE SEE THAT THE |
| | RECESSED LIGHTING IN THE NUMBER AS SHOWN ON PLANS MUST |
| | BE BASED ON THE NUMBER OF FIXTURES AND MAXIMUM WATTAGE |
| | PER FIXTURE. PLEASE SEE THE PREVIOUS CODE 2002 WHICH IS |
| | SECTION 220.3B4. PLEASE SEE 220.14/220.12. |
| | PLEASE KNOW THIS WAS CONFIRMED AT THE SOUTHERN SECTION |
| | MEETING AND BROUGHT FORTH TO THE CODE PANELIST. WHEN A |
| | CONSIDERABLE NUMBER OF RECESSED FIXTURES OR OTHER |
| | FIXTURES ARE SHOWN THEN THE LOADS NEED TO BE SHOWN IN |
| | ADDITION TO THE GENERAL LIGHTING LOADS FIGURED. |
| | PLEASE CALL TO GO OVER. |
| | |
| | 22) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED |
| | LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4. |
| | THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED |
| | SPACE ETC. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |