Plan Review Notes
Plan Review Notes For Permit 08110061
Permit Number 08110061
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-17 13:54:45** FAILED REVIEW **
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE
 LISTED ON ELECTRICAL PLANS FOR DESIGN.
 2005 NFPA-70 ( NEC)
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLANS INDICATE PALM BEACH COUNTY WHEN THE ACTUAL
 APPLIED LOCATION IS IN THE CITY OF WEST PALM BEACH
  
 2) NOTE: PLEASE INDICATE THE AIC RATING OF NEW SERVICE
 EQUIPMENT. 110.9
  
 3) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTOR
 AS REQUIRED PER 250.110,250.6,250.24 IS MISSING. PLEASE
 SEE 250.122 FOR SIZING.
  
 4) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS A
 REQUIRED ATTACHMENT. PLEASE SEE THE RISER INDICATE
 3-#4. WHY IS THERE THREE OF THESE NUMBER FOUR
 CONDUCTORS? IS THIS A MISPRINT?
 PLEASE REVISE.
 PLEASE INCLUDE METALLIC COLD WATER PIPE.
  
 5) NOTE: PLEASE SEE PLANS AS THE SMOKE DETECTION
 DEVICES ARE SHOWN AS *SD*. THERE IS NO SYMBOL LEGEND
 HOWEVER AS A STANDARD OF INDUSTRY THESE WOULD BE SMOKE
 DETECTORS.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V AND
 WOULD DETECT AND SOUND AN ALARM. IF THESE ARE IN FACT
 SMOKE DETECTORS PLEASE INCLUDE THE ENTIRE SYSTEM. IF
 THESE ARE IN FACT SMOKE ALARMS PLEASE ADJUST PLANS.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 6) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN
 NFPA-72 OR CALL TO GO OVER.
 NFPA-72 11.5.1.1, 11.8.3
 AS NOTED IN NOTE #5 ABOVE PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 FOR
 REQUIRED LOADS TO BE FIGURED FOR SMALL APPLIANCE AND
 DINING ROOM RECEPTACLES, BREAKFAST AREAS AND AREAS OF
 THE LIKE. THE LOAD SHOWN AS PORTABLE APPLIANCES IS TOO
 LOW.
  
 8) NOTE: PLEASE SEE 210.11C2, 220.52 AS THE
 WASHER/LAUNDRY CIRCUIT IS ALSO REQUIRED TO BE FIGURED
 FOR A MINIMUM VA LOAD. THE VA LOAD AS SHOWN ON THE
 CALCULATIONS IS TOO LOW.
  
 9) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. THIS HAS
 BEEN REVISED FROM THE 2002 NEC AS STORAGE TYPE WATER
 HEATERS ARE NOW CONSIDERED CONTINUOUS LOADS. PLEASE SEE
 DEFINITIONS IN NEC ARTICLE 100 AND LOADS UNDER
 2154.3,230.42, 220.40 ETC
 ALL CONTINUOUS LOADS ARE REQUIRED TO BE FIGURED AT
 125%. THIS WAS A CHANGE TO THE 2005 CODE.
  
 10) NOTE: PLEASE SEE THE PLANS SEEM TO SHOW A
 RECEPTACLE FOR ONE OF THE WATER HEATERS. PLEASE SEE
 4220.30,422.31 AS THIS IS REQUIRED TO BE A DISCONNECT.
 MAY NOT USE A CORD AND PLUG FOR THE DISCONNECTING MEANS
 FOR THIS LOAD.
  
 11) NOTE: PLEASE SEE 440.11 AS THE A/C EQUIPMENT IS
 MISSING REQUIRED DISCONNECTS. THIS COMMENT IS FOR ALL
 EQUIPMENT. NOT ALL IS SHOWN.
  
 12) NOTE: PLEASE SEE 210.63 FOR MISSING REQUIRED
 SERVICE RECEPTACLE(S).
 PLEASE SEE 210.8A3 FOR OUTDOOR RECEPTACLES WHICH ARE
 REQUIRED TO BE GFI/ GFI PROTECTED.
  
 13) NOTE: PLEASE SEE 210.52C1-5. THERE ARE A COUPLE OF
 RECEPTACLES MISSING ALONG COUNTER SPACES AS SHOWN.
  
 14) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI. AT THIS
 TIME ONLY RECEPTACLES WITHIN 6FT OF THE SINK ARE SHOWN
 AS GFI PROTECTED. THIS CHANGED IN THE 1993 NEC.
  
 15) NOTE: PLEASE LIST THE REQUIRED AFCI ( ARC FAULT)
 PROTECTED CIRCUITS PER 210.12.
 PLEASE KEEP IN MIND THAT ALL OUTLETS INCLUDING
 RECEPTACLES, SMOKE ALARM DEVICES, FANS, LIGHTS ETC ARE
 REQUIRED TO BE PROTECTED.
  
 16) NOTE: PLEASE SEE 424.3B FOR REQUIRED OVER CURRENT
 PROTECTION OF THE HEAT IN THE AIR HANDLING UNITS.
 REQUIRES 125% MINIMUM.
  
 17) NOTE: PLEASE SEE 210.52 FOR SOME MISSING
 RECEPTACLES. PLEASE SEE ONE SET OF PLANS HAS SOME
 REDLINES HOWEVER THESE ARE NOT ALL. PLEASE BE AWARE OF
 THE 2FT, 6FT, 12 FT RULE. SEE PLANS, RECEPTACLES
 REQUIRED WITHIN 6FT OF DOOR.
  
 18) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR REQUIRED
 DEDICATED BATH CIRCUIT(S). MUST BE 20AMP AND #12.
  
 19) NOTE: PLEASE SEE THE REFRIGERATOR IS SHOWN AS #8
 CONDUCTOR ON A 20AMP BREAKER. THIS MUST BE A MISPRINT.
 PLEASE ADJUST.
 PLEASE SEE OTHER CONDUCTOR SIZES ON THE SCHEDULE IF
 THESE ARE SHOWN THEN THE ELECTRICAL CONTRACTOR WILL BE
 REQUIRED TO INSTALL PER PLANS OR PLANS WILL BE REQUIRED
 TO BE REVISED.
 110.3.
 FBC 106.1.1, FOR CLARITY, COORDINATION.
  
 20) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE IS
 REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. PLEASE SEE THE FOLLOWING TEXT WHICH IS
 EXTRACTED DIRECTLY FROM THE 2005 NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.1.1,106.3.5.4,106.5
  
 21) NOTE: THIS COMMENT IS BASED ON UNKNOWN LIGHTING IN
 THE REMAINDER OF THE DWELLING. PLEASE SEE THAT THE
 RECESSED LIGHTING IN THE NUMBER AS SHOWN ON PLANS MUST
 BE BASED ON THE NUMBER OF FIXTURES AND MAXIMUM WATTAGE
 PER FIXTURE. PLEASE SEE THE PREVIOUS CODE 2002 WHICH IS
 SECTION 220.3B4. PLEASE SEE 220.14/220.12.
 PLEASE KNOW THIS WAS CONFIRMED AT THE SOUTHERN SECTION
 MEETING AND BROUGHT FORTH TO THE CODE PANELIST. WHEN A
 CONSIDERABLE NUMBER OF RECESSED FIXTURES OR OTHER
 FIXTURES ARE SHOWN THEN THE LOADS NEED TO BE SHOWN IN
 ADDITION TO THE GENERAL LIGHTING LOADS FIGURED.
 PLEASE CALL TO GO OVER.
  
 22) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED
 LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4.
 THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED
 SPACE ETC.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  