Plan Review Notes
Plan Review Notes For Permit 08110061
Permit Number 08110061
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-26 09:02:572004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. PH#
 561-233-5025
  
 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS.EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL. THE REAR WALL OF THE
 ADDITION IS LESS THAN 6' FROM THE PROPERTY LINE.
 SPECIFY ON THE SITE PLAN THAT THE DISTANCE TO
 STRUCTURES ON ADJACENT PROPERTY IS MORE THAN SIX FEET.
  
 4) SHOW COMPLIANCE WITH R302.2 OPENINGS. OPENINGS SHALL
 NOT BE PERMITTED IN THE EXTERIOR WALL OF A DWELLING OR
 ACCESSORY BUILDING THAT IS SEPARATED FROM AN ADJACENT
 BUILDING BY A DISTANCE OF LESS THAN 6 FEET (1828 MM).
 THIS DISTANCE SHALL BE MEASURED PERPENDICULAR TO THE
 LINE USED TO DETERMINE THE SEPARATION DISTANCE. SEE
 COMMENT #3.
  
 5) PROVIDE A DOOR BUCK FASTENING DETAIL. R613.6
  
 6) FOR THE SECOND FLOOR BEDROOM, SHOW COMPLIANCE WITH
 R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. BASEMENTS
 WITH HABITABLE SPACE AND EVERY SLEEPING ROOM SHALL HAVE
 AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND RESCUE
 OPENING. WHERE EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROVIDED THEY SHALL HAVE A SILL HEIGHT OF NOT MORE THAN
 44 INCHES ABOVE THE FLOOR. THE NET CLEAR OPENING
 DIMENSIONS REQUIRED BY THIS SECTION SHALL BE OBTAINED
 BY THE NORMAL OPERATION OF THE EMERGENCY ESCAPE AND
 RESCUE OPENING FROM THE INSIDE. R310.1.1 MINIMUM
 OPENING AREA. ALL EMERGENCY ESCAPE AND RESCUE OPENINGS
 SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SQUARE
 FEET.
  
 7) SPECIFY THE WINDOW SIZES ON THE PLANS. R301.2.1
  
 8) ALTHOUGH THE STRUCTURE IS LOCATED IN WIND EXPOSURE
 CATEGORY B, SHEET 5 OF THE PLANS SPECIFIES EXPOSURE C.
 THE PRESSURES SPECIFIED ON THE PLANS FOR THE DOORS AND
 WINDOWS ARE FOR EXPOSURE B. PLEASE REVISE. SEE R301.2.1
 AND TABLE R301.2(2).
  
 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) SPECIFY THE FLORIDA PRODUCT APPROVAL FL NUMBERS ON
 THE PLANS FOR THE TRUSS CONNECTORS OR SUBMIT TWO COPIES
 OF PRODUCT APPROVALS FOR THEM. FAC RULE 9B-72.
  
 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT C-740 CASEMENT WINDOWS ARE EXPIRED. PLEASE SUBMIT
 TWO COPIES OF THE CURRENT ONES (NOA 08-0117.11).
  
 12) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 METAL ROOF (NOA 07-0130.06) ARE FOR A STEEL ROOF DECK.
 THE ADDITION HAS A WOOD DECK. SUBMIT TWO COPIES OF THE
 ROOF COVERING PRODUCT APPROVALS FOR INSTALLATION ON A
 WOOD DECK. FAC RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]