Plan Review Notes
Plan Review Notes For Permit 08110008
Permit Number 08110008
Review Stop M
Sequence Number 1
Notes
Date Text
2008-12-07 14:08:06REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. KEYNOTE #40 AND ELECTRICAL PLANS CALL FOR LIGHT
 FIXTURE CONTROLLED BY SWITCH AT ATTIC ACCESS OPENINGS.
 A RECEPTACLE OUTLET IS ALSO REQUIRED AT THESE LOCATIONS
 IN ACCORDANCE WITH FBCR M1305.1.3.1.
  
 2. THE MOCP CALLED FOR ON THE A/C EQUIPMENT SCHEDULE IS
 DIFFERENT FROM THAT CALLED FOR ON THE EELECTRICAL PANEL
 SCHEDULES ON PAGE E-1. PLEASE COORDINATE PLANS SHOWING
 PROPERLY SIZED OCP IN ACCORDANCE WITH FBCR M1401.1.
  
 3. A/C PLANS CALL FOR CONDENSING UNIT SLABS TO BE AT
 GRADE ELEVATION. APPLIANCES INSTALLED AT GRADE LEVEL
 SHALL BE SUPPORTED ON A LEVEL MINIMUM 31/2-INCH
 CONCRETE SLAB EXTENDING A MINIMUM OF 2 INCHES ABOVE
 ADJOINING FINISHED GRADE IN ACCORDANCE WITH FBCR
 M1301.1 AND FBCM 304.9.
  
 4. PLANS CALL FOR A GAS DRYER TO BE INSTALLED IN THE
 LAUNDRY ROOM. SHOW HOW MAKE-UP AND COMBUSTION AIR ARE
 TO BE PROVIDED FOR THIS APPLIANCE IN ACCORDANCE WITH
 FBCR G2407.1 AND G2439.4.
  
 5. SHOW SIZE OF DRYER EXHAUST DUCT AND LOCATION OF
 EXHAUST TERMINATION TO DEMONSTRATE COMPLIANCE WITH FBCR
 G2439.5 AND G2439.5.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]