| 2008-12-07 14:08:06 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. KEYNOTE #40 AND ELECTRICAL PLANS CALL FOR LIGHT |
| | FIXTURE CONTROLLED BY SWITCH AT ATTIC ACCESS OPENINGS. |
| | A RECEPTACLE OUTLET IS ALSO REQUIRED AT THESE LOCATIONS |
| | IN ACCORDANCE WITH FBCR M1305.1.3.1. |
| | |
| | 2. THE MOCP CALLED FOR ON THE A/C EQUIPMENT SCHEDULE IS |
| | DIFFERENT FROM THAT CALLED FOR ON THE EELECTRICAL PANEL |
| | SCHEDULES ON PAGE E-1. PLEASE COORDINATE PLANS SHOWING |
| | PROPERLY SIZED OCP IN ACCORDANCE WITH FBCR M1401.1. |
| | |
| | 3. A/C PLANS CALL FOR CONDENSING UNIT SLABS TO BE AT |
| | GRADE ELEVATION. APPLIANCES INSTALLED AT GRADE LEVEL |
| | SHALL BE SUPPORTED ON A LEVEL MINIMUM 31/2-INCH |
| | CONCRETE SLAB EXTENDING A MINIMUM OF 2 INCHES ABOVE |
| | ADJOINING FINISHED GRADE IN ACCORDANCE WITH FBCR |
| | M1301.1 AND FBCM 304.9. |
| | |
| | 4. PLANS CALL FOR A GAS DRYER TO BE INSTALLED IN THE |
| | LAUNDRY ROOM. SHOW HOW MAKE-UP AND COMBUSTION AIR ARE |
| | TO BE PROVIDED FOR THIS APPLIANCE IN ACCORDANCE WITH |
| | FBCR G2407.1 AND G2439.4. |
| | |
| | 5. SHOW SIZE OF DRYER EXHAUST DUCT AND LOCATION OF |
| | EXHAUST TERMINATION TO DEMONSTRATE COMPLIANCE WITH FBCR |
| | G2439.5 AND G2439.5.1. |
| | |