| Plan Review Notes For Permit 08110006 |
| Permit Number |
08110006 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-12-30 16:54:38 | ** DENIED REVIEW ** | | | | | | | | | ** SHEET E3.1 AND 4.1 WERE OK. | | | REDLINED: WIRING METHOD ALLOWED BY NEC 645 ARE NOT | | | PERMITTED IN THE PHONE ROOM. CHAPTERS 1-4 APPLY ON | | | WIRING. | | | | | | 1) NOTE: PLEASE SEE ROOM 902 IS MISSING CONTROLS PER | | | FBC 13-415.1.ABC.1.1, .1.2. THIS WAS NOT ON PREVIOUS | | | REVIEWED PLANS. PLEASE SHOW CONTROLS PER SECTIONS FOR | | | CONFERENCE ROOMS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|