| 2008-11-10 13:53:47 | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1,.1.2. |
| | PLEASE SEE THE LPC SUBMITTED DO NOT COORDINATE WITH |
| | PLANS AND FIXTURE LEGEND. PLEASE SEE THE FIXTURE LEGEND |
| | AND THE WATTAGES SHOWN. PLEASE SEE THE CALCULATIONS |
| | SUBMITTED ONLY INDICATE TWO FIXTURES. |
| | |
| | 2) NOTE: PLEASE SEE 408.36, 240.21 AND 310.16 AS THE |
| | TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE |
| | TRANSFORMER ARE REQUIRED TO TERMINATE IN OVER CURRENT |
| | PROTECTION. |
| | |
| | 3) NOTE: PLEASE INDICATE THE CONTINUOUS LOADS AT 125%. |
| | 230.42,215.3 ETC. |
| | PLEASE SEE 422.13 FOR ANY STORAGE TYPE WATER HEATERS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |