| Date |
Text |
| 2009-11-25 09:29:56 | NOC HAS EXPIRED, ONLY NOTED FOR CONTRACTOR. |
| 2009-11-25 09:29:14 | * PROVISO ** |
| | |
| | ** REVIEW UNDER THE 2004 FBC W/ 2006/2007 REVISIONS. |
| | |
| | ** THE CONDITIONS FOR PROVISO ARE GIVEN TO HAVE PLANS |
| | REVISED AND SUBMITTED FOR REVIEW WITHIN 30DAYS OF |
| | ISSUANCE OF PERMIT FOR BASE BUILDING. |
| | |
| | ** THE GENERATOR AND ATS ARE NOT INCLUDED AND SHALL BE |
| | UNDER SEPARATE PERMITS. NO REVIEW IS DONE FOR LOCATION |
| | OR CODE COMPLIANCE. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE REVISE AND SUBMIT SIGNED, DATED AND |
| | SEALED PHOTO-METRICS FOR EGRESS PATHS FOR NORMAL |
| | OPERATION AS WELL AS EMERGENCY. |
| | FBC 1016.1.2, NFPA-101 7.8.1.3, 7.9.1.2,.2.2. |
| | |
| | 2) NOTE: LIGHTING KEY NOTES NOTE #2 STATES TO |
| | WIRE/CIRCUIT ALL EMERGENCY LIGHT FIXTURES TO LOCAL |
| | BRANCH CIRCUIT PER 700.12F ( EXCEPTION). CAN NOT WIRE |
| | PER EXCEPTIONS AS NO AREAS ON PLANS MEET EXCEPTION |
| | LISTED IN THE NFPA-70 ( NATIONAL ELECTRICAL CODE). |
| | CIRCUITING ON PLANS INDICATES C-1, HOWEVER THE PLANS DO |
| | NOT MEET EXCEPTION IN SECTION TO WIRE ALL FIXTURES TO |
| | ONE CIRCUIT. |
| | THE E3 FIXTURES FOR EXAMPLE ARE SHOWN TO BE CIRCUITED |
| | TO SEPARATE CIRCUIT THAN THE OTHER NORMAL LIGHTING IN |
| | THE STAIR AREAS ON THE OUTSIDE OF THE BUILDING. |
| | CIRCUITING NEEDS TO BE REVISED. |
| | |
| | 3) NOTE: LIGHTING CONTROLS PER 13-415.1.ABC.1.1,.1.2, |
| | .1.3 NEED TO BE ADJUSTED FOR CODE COMPLIANCE. |
| | |
| | A) DISPLAY AREAS ARE NOT SHOWING ANY SEPARATE SPACE |
| | CONTROLS OR CONTROLS FOR SEPARATE DISPLAY/ACCENT |
| | LIGHTING AREAS. PLEASE SEE 13-415.1.ABC.1.1 AND .1.3 |
| | |
| | B) JANITOR/STORAGE CLOSETS ARE REQUIRED TO BE AUTOMATED |
| | LIGHTING CONTROLS OF SOME KIND. THESE ARE NOT AREAS |
| | CLASSIFIED TO MEET ANY OF THE EXCEPTIONS IN THE CODE. |
| | ** ADJUST CALCULATIONS FOR SPACES AND TYPES OF |
| | CONTROLS. ROOMS ARE 211,133, 118 ETC |
| | |
| | C) PLEASE SEE 13-415.1.ABC.1.1 |
| | SECTION 1: SEPARATE LIGHTING CONTROLS REQUIRED FOR MORE |
| | THAN ONE FLOOR. RISER INDICATES RELAY PANELS FOR EACH |
| | FLOOR HOWEVER PLEASE ADJUST SCHEDULES TO SEPARATE |
| | FLOORS/CIRCUITING. |
| | AS SHOWN AT THIS TIME SEPARATION OF AREAS/CONTROLS FOR |
| | EACH FLOOR NEED TO BE IDENTIFIED TO SHOW SEPARATION. |
| | |
| | 4) NOTE: ** THE SUBMITTED FLA COM CALCULATIONS ARE |
| | WITHOUT GROSS ERRORS AS STATED IN 13-103.3. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1, |
| | 13-415.2.ABC.1.1,.1.2 ETC THE USE OF *MANUAL ON/OFF* IS |
| | NOT APPLICABLE TO AREAS AS DESIGNATED ON PLANS AND THE |
| | INPUT DATA REPORT. |
| | ONLY AREAS WHICH ACTUALLY MEET EXCEPTIONS FOR *MANUAL |
| | ON/OFF* CAN BE DESIGNATED IN THE IDR FOR SUCH. THIS |
| | DOES NOT AFFECT THE CALCULATIONS FOR LESS EFFICIENCY. |
| | THE USE OF FOOD SERVICE FOR EMPLOYEE BREAK ROOM IS NOT |
| | ACCURATE. THIS WOULD BE OFFICE/GENERAL LIGHTING. |
| | |
| | 5) NOTE: WIND LOAD CALCULATIONS AND INFORMATION MUST BE |
| | SUBMITTED FOR SITE LIGHTING POLES MEETING CHAPTER 16 OF |
| | THE FBC. WIND LOAD CALCULATIONS WILL BE REQUIRED TO BE |
| | SIGNED, DATED AND SEALED BY A FLORIDA REGISTERED |
| | ENGINEER. THESE WILL BE REVIEWED BY THE BUILDING PLANS |
| | EXAMINER. |
| | |
| | 6) NOTE: ** NOTED ONLY FOR INFORMATION. PLEASE SEE ASME |
| | A17.1 2004 AS ADOPTED BY THE FBC. THE ELEVATOR CODE HAS |
| | BEEN REVISED FOR SEVERAL AREAS INCLUDING LIGHTING |
| | LEVELS IN ELEVATOR EQUIPMENT ROOMS, PIT AREAS, LANDINGS |
| | ETC. |
| | BASED ON PLANS, LIGHTING LEVELS DO NOT APPEAR TO MEET |
| | MINIMUMS. |
| | ** THIS IS ONLY NOTED FOR INFORMATION TO ALLEVIATE ANY |
| | HARDSHIPS/DELAYS FOR THE TCO OR CO CONDITIONS WHEN |
| | ELEVATOR AND EQUIPMENT IS INSPECTED BY THE STATE. |
| | ** THESE ITEMS ARE NOT UNDER THE REVIEW OF THE |
| | CONSTRUCTION SERVICES DEPARTMENT AND IS GIVEN FOR |
| | INFORMATION ONLY. IF THERE ARE QUESTIONS, PLEASE CALL. |
| | |
| | 7) NOTE: TANK-LESS WATER HEATERS ON PLANS INDICATE |
| | TOTAL KW AS 9.6 YET FLA COM INDICATES 8KW. PLEASE |
| | ADJUST.13-412. |
| | |
| | 8) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR ADA |
| | COMPLIANCE OF HORN AND STROBE DEVICES PER 11-4.28.1,.2 |
| | AND.3 (4). |
| | THE HEIGHTS ARE SHOWN ON LEGEND HOWEVER NOT LEVELS FOR |
| | CANDELA AND DB LEVELS. |
| | PLEASE KNOW THAT ALL FIRE ALARM PERMITS/FIRE SPRINKLERS |
| | ARE ALSO UNDER SEPARATE PERMITS. |
| | |
| | 9) NOTE: **ALL LOW VOLTAGE PERMIT ARE SEPARATE. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |