Plan Review Notes
Plan Review Notes For Permit 08100686
Permit Number 08100686
Review Stop E
Sequence Number 2
Notes
Date Text
2009-11-25 09:29:56NOC HAS EXPIRED, ONLY NOTED FOR CONTRACTOR.
2009-11-25 09:29:14* PROVISO **
  
 ** REVIEW UNDER THE 2004 FBC W/ 2006/2007 REVISIONS.
  
 ** THE CONDITIONS FOR PROVISO ARE GIVEN TO HAVE PLANS
 REVISED AND SUBMITTED FOR REVIEW WITHIN 30DAYS OF
 ISSUANCE OF PERMIT FOR BASE BUILDING.
  
 ** THE GENERATOR AND ATS ARE NOT INCLUDED AND SHALL BE
 UNDER SEPARATE PERMITS. NO REVIEW IS DONE FOR LOCATION
 OR CODE COMPLIANCE.
  
  
  
 1) NOTE: PLEASE REVISE AND SUBMIT SIGNED, DATED AND
 SEALED PHOTO-METRICS FOR EGRESS PATHS FOR NORMAL
 OPERATION AS WELL AS EMERGENCY.
 FBC 1016.1.2, NFPA-101 7.8.1.3, 7.9.1.2,.2.2.
  
 2) NOTE: LIGHTING KEY NOTES NOTE #2 STATES TO
 WIRE/CIRCUIT ALL EMERGENCY LIGHT FIXTURES TO LOCAL
 BRANCH CIRCUIT PER 700.12F ( EXCEPTION). CAN NOT WIRE
 PER EXCEPTIONS AS NO AREAS ON PLANS MEET EXCEPTION
 LISTED IN THE NFPA-70 ( NATIONAL ELECTRICAL CODE).
 CIRCUITING ON PLANS INDICATES C-1, HOWEVER THE PLANS DO
 NOT MEET EXCEPTION IN SECTION TO WIRE ALL FIXTURES TO
 ONE CIRCUIT.
 THE E3 FIXTURES FOR EXAMPLE ARE SHOWN TO BE CIRCUITED
 TO SEPARATE CIRCUIT THAN THE OTHER NORMAL LIGHTING IN
 THE STAIR AREAS ON THE OUTSIDE OF THE BUILDING.
 CIRCUITING NEEDS TO BE REVISED.
  
 3) NOTE: LIGHTING CONTROLS PER 13-415.1.ABC.1.1,.1.2,
 .1.3 NEED TO BE ADJUSTED FOR CODE COMPLIANCE.
  
 A) DISPLAY AREAS ARE NOT SHOWING ANY SEPARATE SPACE
 CONTROLS OR CONTROLS FOR SEPARATE DISPLAY/ACCENT
 LIGHTING AREAS. PLEASE SEE 13-415.1.ABC.1.1 AND .1.3
  
 B) JANITOR/STORAGE CLOSETS ARE REQUIRED TO BE AUTOMATED
 LIGHTING CONTROLS OF SOME KIND. THESE ARE NOT AREAS
 CLASSIFIED TO MEET ANY OF THE EXCEPTIONS IN THE CODE.
 ** ADJUST CALCULATIONS FOR SPACES AND TYPES OF
 CONTROLS. ROOMS ARE 211,133, 118 ETC
  
 C) PLEASE SEE 13-415.1.ABC.1.1
 SECTION 1: SEPARATE LIGHTING CONTROLS REQUIRED FOR MORE
 THAN ONE FLOOR. RISER INDICATES RELAY PANELS FOR EACH
 FLOOR HOWEVER PLEASE ADJUST SCHEDULES TO SEPARATE
 FLOORS/CIRCUITING.
 AS SHOWN AT THIS TIME SEPARATION OF AREAS/CONTROLS FOR
 EACH FLOOR NEED TO BE IDENTIFIED TO SHOW SEPARATION.
  
 4) NOTE: ** THE SUBMITTED FLA COM CALCULATIONS ARE
 WITHOUT GROSS ERRORS AS STATED IN 13-103.3.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1,
 13-415.2.ABC.1.1,.1.2 ETC THE USE OF *MANUAL ON/OFF* IS
 NOT APPLICABLE TO AREAS AS DESIGNATED ON PLANS AND THE
 INPUT DATA REPORT.
 ONLY AREAS WHICH ACTUALLY MEET EXCEPTIONS FOR *MANUAL
 ON/OFF* CAN BE DESIGNATED IN THE IDR FOR SUCH. THIS
 DOES NOT AFFECT THE CALCULATIONS FOR LESS EFFICIENCY.
 THE USE OF FOOD SERVICE FOR EMPLOYEE BREAK ROOM IS NOT
 ACCURATE. THIS WOULD BE OFFICE/GENERAL LIGHTING.
  
 5) NOTE: WIND LOAD CALCULATIONS AND INFORMATION MUST BE
 SUBMITTED FOR SITE LIGHTING POLES MEETING CHAPTER 16 OF
 THE FBC. WIND LOAD CALCULATIONS WILL BE REQUIRED TO BE
 SIGNED, DATED AND SEALED BY A FLORIDA REGISTERED
 ENGINEER. THESE WILL BE REVIEWED BY THE BUILDING PLANS
 EXAMINER.
  
 6) NOTE: ** NOTED ONLY FOR INFORMATION. PLEASE SEE ASME
 A17.1 2004 AS ADOPTED BY THE FBC. THE ELEVATOR CODE HAS
 BEEN REVISED FOR SEVERAL AREAS INCLUDING LIGHTING
 LEVELS IN ELEVATOR EQUIPMENT ROOMS, PIT AREAS, LANDINGS
 ETC.
 BASED ON PLANS, LIGHTING LEVELS DO NOT APPEAR TO MEET
 MINIMUMS.
 ** THIS IS ONLY NOTED FOR INFORMATION TO ALLEVIATE ANY
 HARDSHIPS/DELAYS FOR THE TCO OR CO CONDITIONS WHEN
 ELEVATOR AND EQUIPMENT IS INSPECTED BY THE STATE.
 ** THESE ITEMS ARE NOT UNDER THE REVIEW OF THE
 CONSTRUCTION SERVICES DEPARTMENT AND IS GIVEN FOR
 INFORMATION ONLY. IF THERE ARE QUESTIONS, PLEASE CALL.
  
 7) NOTE: TANK-LESS WATER HEATERS ON PLANS INDICATE
 TOTAL KW AS 9.6 YET FLA COM INDICATES 8KW. PLEASE
 ADJUST.13-412.
  
 8) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR ADA
 COMPLIANCE OF HORN AND STROBE DEVICES PER 11-4.28.1,.2
 AND.3 (4).
 THE HEIGHTS ARE SHOWN ON LEGEND HOWEVER NOT LEVELS FOR
 CANDELA AND DB LEVELS.
 PLEASE KNOW THAT ALL FIRE ALARM PERMITS/FIRE SPRINKLERS
 ARE ALSO UNDER SEPARATE PERMITS.
  
 9) NOTE: **ALL LOW VOLTAGE PERMIT ARE SEPARATE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved