| 2008-11-06 15:42:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | |
| | 1) SUBMIT ENERGY CALCULATIONS FOR REVIEW, PER 2004 FBC |
| | 13-101.1.1. |
| | |
| | 2) SUBMIT COOLING LOAD CALCULATIONS FOR REVIEW, PER |
| | 2004 FBC 13-407.1.ABC.1. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| | A/C SYSTEMS, PER 2004 FBC/M 304.1 AND FBC |
| | 13-407.1.ABC.1.1. |
| | |
| | 4) SHOW THE SEER OF EACH SYSTEM IN THE EQUIPMENT |
| | SCHEDULE, SEE 2004 FBC 13-407.1.ABC.3.1.1. |
| | |
| | 5) THERE ARE 37 AIR HANDLER UNITS BEING INSTALLED, |
| | PLEASE NUMBER THEM ON THE PLAN FROM 1 TO 37, AND SHOW |
| | ON THE EQUIPMENT SCHEDULE WHICH AIR HANDLER GOES TO |
| | WHICH CONDENSER UNIT, SEE 2004 FBC 13-407.1.ABC.2.1.1. |
| | |
| | 6) NEED TO PROVIDE OUTSIDE AIR TO OFFICES 1 & 2 ON THE |
| | FIRST FLOOR AND THE EMPLOYEES LOUNGE ON THE SECOND |
| | FLOOR, PER 2004 FBC/M 401.2. |
| | |
| | 7) TWO A/C DUCTS ARE PENETRATING A RATED WALL BETWEEN |
| | THE RETAIL ROOM 112 AND DISPLAY WINDOW 4 AREA FIRE |
| | DAMPERS NEED TO BE INSTALLED OR MEAT THE EXCEPTIONS OF |
| | 2004 FBC/M 607.5.2. |
| | |
| | 8) PLAN M4.1 "SEQUENCE OF OPERATION" NOTES STATES THE |
| | UNITS HOT GAS REHEAT SOLENOID VALVE SHALL BE ENERGIZED |
| | TO MAINTAIN ADJUSTABLE HUMIDITY SETPOINT SETTINGS. |
| | PLEASE SHOW COMPLIANCE WITH 2004 FBC 13-407.1.ABC.2.2 |
| | HOT GAS BYPASS LIMITATION. |
| | |
| | 9) AIR HANDLER 10 IS 100% OUTDOOR AIR AND NEEDS TO |
| | COMPLY WITH 2004 FBC 13-409.1.ABC.3.3 SHUTOFF DAMPER |
| | CONTROLS. BOTH OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS |
| | SHALL BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL |
| | AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED |
| | ARE NOT IN USE. VENTILATION OUTSIDE AIR DAMPERS SHALL |
| | BE CAPABLE OF AUTOMATICALLY SHUTTING OFF DURING |
| | PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND SETBACK, |
| | EXCEPT WHEN VENTILATION REDUCES ENERGY COSTS (E.G., |
| | NIGHT PURGE) OR WHEN VENTILATION MUST BE SUPPLIED TO |
| | MEET CODE REQUIREMENTS. EXCEPTIONS: 1. GRAVITY |
| | (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN BUILDING |
| | EXHAUST AIR SYSTEMS. PLEASE ALSO ADJUST THE NOTES IN |
| | THE "SEQUENCE OF OPERATION" ON PLAN M4.1. |
| | |
| | 10) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA ON THE |
| | OUTDOOR WALL LOUVERS FOR THE OUTSIDE AIR INTAKE AND THE |
| | 36X10 RELIEF AIR DUCTS, SEE FS 553.842(1) AND FAC RULE |
| | 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |
| | *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND |
| | SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. |
| | AMEND. 106.3. |
| | |
| | MECHANICAL PLAN REVIEW BY; |