Plan Review Notes
Plan Review Notes For Permit 08100686
Permit Number 08100686
Review Stop M
Sequence Number 1
Notes
Date Text
2008-11-06 15:42:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) SUBMIT ENERGY CALCULATIONS FOR REVIEW, PER 2004 FBC
 13-101.1.1.
  
 2) SUBMIT COOLING LOAD CALCULATIONS FOR REVIEW, PER
 2004 FBC 13-407.1.ABC.1.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 A/C SYSTEMS, PER 2004 FBC/M 304.1 AND FBC
 13-407.1.ABC.1.1.
  
 4) SHOW THE SEER OF EACH SYSTEM IN THE EQUIPMENT
 SCHEDULE, SEE 2004 FBC 13-407.1.ABC.3.1.1.
  
 5) THERE ARE 37 AIR HANDLER UNITS BEING INSTALLED,
 PLEASE NUMBER THEM ON THE PLAN FROM 1 TO 37, AND SHOW
 ON THE EQUIPMENT SCHEDULE WHICH AIR HANDLER GOES TO
 WHICH CONDENSER UNIT, SEE 2004 FBC 13-407.1.ABC.2.1.1.
  
 6) NEED TO PROVIDE OUTSIDE AIR TO OFFICES 1 & 2 ON THE
 FIRST FLOOR AND THE EMPLOYEES LOUNGE ON THE SECOND
 FLOOR, PER 2004 FBC/M 401.2.
  
 7) TWO A/C DUCTS ARE PENETRATING A RATED WALL BETWEEN
 THE RETAIL ROOM 112 AND DISPLAY WINDOW 4 AREA FIRE
 DAMPERS NEED TO BE INSTALLED OR MEAT THE EXCEPTIONS OF
 2004 FBC/M 607.5.2.
  
 8) PLAN M4.1 "SEQUENCE OF OPERATION" NOTES STATES THE
 UNITS HOT GAS REHEAT SOLENOID VALVE SHALL BE ENERGIZED
 TO MAINTAIN ADJUSTABLE HUMIDITY SETPOINT SETTINGS.
 PLEASE SHOW COMPLIANCE WITH 2004 FBC 13-407.1.ABC.2.2
 HOT GAS BYPASS LIMITATION.
  
 9) AIR HANDLER 10 IS 100% OUTDOOR AIR AND NEEDS TO
 COMPLY WITH 2004 FBC 13-409.1.ABC.3.3 SHUTOFF DAMPER
 CONTROLS. BOTH OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS
 SHALL BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED
 ARE NOT IN USE. VENTILATION OUTSIDE AIR DAMPERS SHALL
 BE CAPABLE OF AUTOMATICALLY SHUTTING OFF DURING
 PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND SETBACK,
 EXCEPT WHEN VENTILATION REDUCES ENERGY COSTS (E.G.,
 NIGHT PURGE) OR WHEN VENTILATION MUST BE SUPPLIED TO
 MEET CODE REQUIREMENTS. EXCEPTIONS: 1. GRAVITY
 (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN BUILDING
 EXHAUST AIR SYSTEMS. PLEASE ALSO ADJUST THE NOTES IN
 THE "SEQUENCE OF OPERATION" ON PLAN M4.1.
  
 10) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA ON THE
 OUTDOOR WALL LOUVERS FOR THE OUTSIDE AIR INTAKE AND THE
 36X10 RELIEF AIR DUCTS, SEE FS 553.842(1) AND FAC RULE
 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;