| 2008-12-03 11:23:42 | RETAIL / WAREHOUSE |
| | 3415 SOUTH DIXIE HIGHWAY |
| | |
| | 1. PLEASE INCLUDE THE FLORIDA FIRE PREVENTION CODE IN |
| | THE APPLICABLE CODES SECTION ON PAGE C1. |
| | |
| | 2. CONSTRUCTION, RENOVATION, AND DEMOLITION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 3. PLEASE SUBMIT SEPARATE PLANS AND PERMITS FOR THE |
| | INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER SYSTEM. |
| | |
| | 4. IN SOME CASES ON PAGE A2 TRAVEL DISTANCE ROUTES |
| | APPEAR TO PASS THROUGH SOLID WALLS. |
| | |
| | 5. A KNOX-BOX AND KNOX LOCKING CAPS WILL BE REQUIRED |
| | FOR THE PROJECT. APPLICATIONS CAN BE OBTAINED FROM |
| | CENTRAL FIRE STATION, 804-4724. |
| | |
| | 6. SEPERATE PLANS AND PERMITS WILL BE REQUIRED FOR THE |
| | INSTALLATION OF THE FIRE ALARM SYSTEM. THE FIRE ALARM |
| | SYSTEM WILL BE REQUIRED TO BE MONITORED BY A UL LISTED |
| | CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE. |
| | |
| | 7. PLEASE EXPLAIN EXISTING. EXITING APPEARS TO PASS |
| | THROUGH WAREHOUSE AREAS. HOW ILL EXIT ACCESS BE |
| | MAINTAINED IN THESE AREAS USED FOR STORAGE PURPOSES. |
| | WHAT METHODS OR DEVICES ARE PLANNED TO MAINTAIN EXIT |
| | ACCESS. |
| | |
| | 8. IT APPEARS THAT ADDITIONAL EMERGENCY LIGHT FIXTURES |
| | ARE NEEDED IN SOME OF THE EXIT ACCESS AREAS. |
| | |
| | 9. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS. |
| | |
| | 10. WHAT TYPES OF MATERIALS ARE PLANNED TO BE STORED IN |
| | THE WAREHOUSE AREAS. |
| | |
| | 11. TACTILE SIGNAGE REQUIRED AT EXIT LOCATIONS. |
| | |
| | 12. ELEVATOR WARNING SIGNS ARE TO BE PROVIDED. |
| | |
| | 13. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A |
| | MINIMUM OF AT LEAST 6" HIGH AND 1" WIDE NUMBERS ARE |
| | REQUIRED. |
| | |
| | 14. NO COMBUSTIBLE MATERIALS ALLOWED IN THE RETURN AIR |
| | PLENUM. |
| | |
| | 15. PLEASE DISPLAY ALL PROPOSED FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |
| | 16. PLEASE R EVIEW DOOR SCHEDULE AND WALL DETAILS. THE |
| | DOOR SCHEDULE DECLARES 90 MINUTE C LABEL BUT SHOULD |
| | READ 90 MINUTE B LABELED. THE PROPER RATING OF DOORS |
| | SHALL BE INSTALLED IN THE APPROPRIATE WALL TYPES. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |