Plan Review Notes
Plan Review Notes For Permit 08100686
Permit Number 08100686
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-10 09:58:55 
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WITH THE
 LIGHTING PERFORMANCE. PLEASE KNOW BASED ON THE
 FOLLOWING COMMENT THE USE AND OCCUPANCY SHALL BE
 COORDINATED. THE MAIN OCCUPANCY IS WAREHOUSE.
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE BE SURE TO SEE REQUIRED ALLOWANCES FOR TRACK
 LIGHTING.
  
 2) NOTE: THE OCCUPANCY AS SHOWN IS IN QUESTION. THE
 PLANS INDICATE *WAREHOUSE* IN MOST LOCATIONS WITH ONLY
 FOUR SMALLER AREAS AS *RETAIL*. HOWEVER THE LIGHTING
 FIXTURE SCHEDULE ALONG WITH LIGHTING IN THE BUILDING
 LENDS TO ALL BEING RETAIL. THE LOAD CALCULATIONS ARE
 ALSO SUBMITTED AND SHOWN AS RETAIL. A CALL WAS PLACED
 TO THE ARCHITECT AND ENGINEERS OFFICE AS THE USE OF
 LIGHTING AND OTHER ALLOWANCES WOULD BE REQUIRED TO BE
 FIGURED ON THE WAREHOUSE. PLANS INDICATE RETAIL IN
 NUMEROUS LOCATIONS INCLUDING RETAIL LIGHTING, RETAIL
 DECRETIVE LIGHTS ETC.
 IF THIS IS RETAIL OCCUPANCY PLEASE ADJUST PLAN
 ACCORDINGLY.
 FBC 301.1
 FBC 13-415.2
 NEC 220
  
 3) NOTE: PLEASE SUBMIT EGRESS PHOTO-METRICS UNDER
 NORMAL AND EMERGENCY LEVELS FOR EGRESS PATHS. PLEASE
 SEE NFPA-101 7.8.1.3, 7.9.1.2, .2.2. STAIRS SHALL BE
 10FT CANDLE UNDER NORMAL AND 1FT CANDLE UNDER
 EMERGENCY.
  
 4) NOTE: THE RISER IS CONFUSING AND UNCLEAR AT THIS
 TIME. THE RISER CLEARLY SHOWS A NEW MAIN WHICH HAS THE
 SERVICE ENTRANCE CONDUITS FROM FPL TO MAIN. THESE ARE
 THREE CONDUITS WITH 400MCM. THE RISER THEN SHOWS A
 KEYNOTE #8 WHICH APPEARS TO BE FROM THE ATS TO MDP
 HOWEVER AS NO CONDUIT OR KEYNOTE IS SHOWN FROM THE MAIN
 TO THE ATS IT IS UNCLEAR AT THIS TIME OF THE SIZES ETC.
 AS SHOWN FROM THE ATS TO THE MDP THE KEY NOTE #8 THERE
 IS ONLY TWO SETS OF 400MCM. BASED ON 310.16 AND 240.4B
 THESE ARE OF INSUFFICIENT SIZE. THE MDP SCHEDULE NOTES
 THREE SETS. IT IS UNCLEAR HOW THE ATS CAN BE FUTURE
 WHEN THE RISER INDICATES THE CONDUITS FROM THE MAIN TO
 THE ATS AND THEN TO THE MAIN DISTRIBUTION PANEL. IF THE
 ATS WILL NOT BE INSTALLED AT THIS TIME THEN THE
 CONDUITS NEED TO BE SHOWN FROM MAIN TO THE MLO MDP. IF
 THE ATS WILL BE INSTALLED AT THIS TIME PLEASE SUBMIT
 THE MANUFACTURE SPECS/CUT SHEETS.
 PLEASE ALSO SEE THE RISER HAS KEYNOTES NUMBERED UP TO
 AND INCLUDING #13 HOWEVER THE RISER KEYNOTES ONLY STATE
 NOTES UP TO #11
 PLEASE ADJUST RISER AS NEEDED.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 WITH RESPECT
 TO LIGHTING CONTROLS ON EACH FLOOR. PLEASE SUBMIT MORE
 INFORMATION ON THE PROPOSED LIGHTING CONTROL SYSTEM.
 PLEASE SHOW ALL OVER RIDE LOCATIONS FOR THE OCCUPANT TO
 SEE THE LIGHTING WHICH IS BEING CONTROLLED OR SHOW A
 DETAIL ON THE EXCEPTION TO THIS.
  
 6) NOTE: PLEASE SEE 13-415.1.ABC.1.4. THE PLANS CONTAIN
 A NOTE FOR OUTSIDE LIGHTING TO BE ROUTED THROUGH AN
 ASTRONOMICAL TIME CLOCK HOWEVER PLEASE INDICATE THE
 REQUIRED BACK UP FOR PROGRAMMING. THE CODE SECTION
 GIVEN REQUIRES A MINIMUM OF 10HRS. THIS MAY BE MORE
 HOWEVER AT LEAST 10HRS.
  
 7) NOTE: PLEASE SEE 422.13 (2005 NEC) AS STORAGE TYPE
 WATER HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD AND
 NEEDS TO BE FIGURED AT 125%. PLEASE ADJUST LOAD
 CALCULATIONS.
  
 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ALL
 DEVICES FOR ANY FIRE ALARM SYSTEM. PLANS NEED TO
 INDICATE ALL LOCATIONS, HEIGHTS AND THE LEVELS OF THE
 DEVICES FOR ADA COMPLIANCE.
  
 9) NOTE: PLEASE SEE 250.50, 250.66, 250.53, ETC. THE
 SIZE OF THE GROUNDING ELECTRODE CONDUCTOR TO THE FOOTER
 STEEL IS REQUIRED TO BE THE SAME SIZE OF THE GROUNDING
 ELECTRODE BASED ON THE SERVICE ENTRANCE CONDUCTORS. THE
 NOTES ON RISER CONTAIN A 3/0 WHICH IS OK HOWEVER AS THE
 SYSTEM IS CONTINUOUS WITH MORE THAN ONE ATTACHMENT THE
 SIZE FOR THE FOOTER ALSO NEEDS TO BE 3/0. ONLY WHEN THE
 SOLE CONNECTION IS TO THE FOOTER AND NO OTHER
 ATTACHMENTS DOES THE CODE PERMIT THE #4 TO BE THE
 LARGEST. PLEASE SEE HANDBOOK WHICH SHOWS THE *MINIMUM*
 SIZE OF #4.
  
 10) NOTE: THE RISER NOTES TO SEE PANELS FOR FEEDERS AND
 CONDUIT SIZES HOWEVER THESE FEEDERS ETC AS NOTED ON
 EACH PANEL DOES NOT PROVIDE THE EQUIPMENT GROUNDING
 CONDUCTORS. PLEASE PROVIDE THE EQUIPMENT GROUNDING
 CONDUCTORS.
 250.122, 250.110, ETC
  
 11) NOTE: COLOR CODING FOR 277/480V WOULD NEED TO BE
 BROWN, PURPLE, YELLOW. THIS COULD BE REDLINED AS THERE
 ARE NO 277/480V SYSTEMS ON THE PLANS. IN THE CODE
 ORANGE IS FOR HIGH-LEG SYSTEMS.
 THIS IS NOTED FOR INFORMATION ONLY.
  
 12) NOTE: THE LOAD CALCULATIONS INDICATE THE
 REQUIREMENT FOR SHOW WINDOWS HOWEVER PLEASE SEE 220.43B
 AND PLEASE SHOW HOW LOAD WAS FIGURED.
  
 ** IT IS IMPORTANT TO KNOW AS THERE IS SOME INFORMATION
 NOT YET SUBMITTED THERE MAY VERY WELL BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH COULD NOT BE MADE AT THIS
 TIME.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  