| 2008-11-10 09:58:55 | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WITH THE |
| | LIGHTING PERFORMANCE. PLEASE KNOW BASED ON THE |
| | FOLLOWING COMMENT THE USE AND OCCUPANCY SHALL BE |
| | COORDINATED. THE MAIN OCCUPANCY IS WAREHOUSE. |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE BE SURE TO SEE REQUIRED ALLOWANCES FOR TRACK |
| | LIGHTING. |
| | |
| | 2) NOTE: THE OCCUPANCY AS SHOWN IS IN QUESTION. THE |
| | PLANS INDICATE *WAREHOUSE* IN MOST LOCATIONS WITH ONLY |
| | FOUR SMALLER AREAS AS *RETAIL*. HOWEVER THE LIGHTING |
| | FIXTURE SCHEDULE ALONG WITH LIGHTING IN THE BUILDING |
| | LENDS TO ALL BEING RETAIL. THE LOAD CALCULATIONS ARE |
| | ALSO SUBMITTED AND SHOWN AS RETAIL. A CALL WAS PLACED |
| | TO THE ARCHITECT AND ENGINEERS OFFICE AS THE USE OF |
| | LIGHTING AND OTHER ALLOWANCES WOULD BE REQUIRED TO BE |
| | FIGURED ON THE WAREHOUSE. PLANS INDICATE RETAIL IN |
| | NUMEROUS LOCATIONS INCLUDING RETAIL LIGHTING, RETAIL |
| | DECRETIVE LIGHTS ETC. |
| | IF THIS IS RETAIL OCCUPANCY PLEASE ADJUST PLAN |
| | ACCORDINGLY. |
| | FBC 301.1 |
| | FBC 13-415.2 |
| | NEC 220 |
| | |
| | 3) NOTE: PLEASE SUBMIT EGRESS PHOTO-METRICS UNDER |
| | NORMAL AND EMERGENCY LEVELS FOR EGRESS PATHS. PLEASE |
| | SEE NFPA-101 7.8.1.3, 7.9.1.2, .2.2. STAIRS SHALL BE |
| | 10FT CANDLE UNDER NORMAL AND 1FT CANDLE UNDER |
| | EMERGENCY. |
| | |
| | 4) NOTE: THE RISER IS CONFUSING AND UNCLEAR AT THIS |
| | TIME. THE RISER CLEARLY SHOWS A NEW MAIN WHICH HAS THE |
| | SERVICE ENTRANCE CONDUITS FROM FPL TO MAIN. THESE ARE |
| | THREE CONDUITS WITH 400MCM. THE RISER THEN SHOWS A |
| | KEYNOTE #8 WHICH APPEARS TO BE FROM THE ATS TO MDP |
| | HOWEVER AS NO CONDUIT OR KEYNOTE IS SHOWN FROM THE MAIN |
| | TO THE ATS IT IS UNCLEAR AT THIS TIME OF THE SIZES ETC. |
| | AS SHOWN FROM THE ATS TO THE MDP THE KEY NOTE #8 THERE |
| | IS ONLY TWO SETS OF 400MCM. BASED ON 310.16 AND 240.4B |
| | THESE ARE OF INSUFFICIENT SIZE. THE MDP SCHEDULE NOTES |
| | THREE SETS. IT IS UNCLEAR HOW THE ATS CAN BE FUTURE |
| | WHEN THE RISER INDICATES THE CONDUITS FROM THE MAIN TO |
| | THE ATS AND THEN TO THE MAIN DISTRIBUTION PANEL. IF THE |
| | ATS WILL NOT BE INSTALLED AT THIS TIME THEN THE |
| | CONDUITS NEED TO BE SHOWN FROM MAIN TO THE MLO MDP. IF |
| | THE ATS WILL BE INSTALLED AT THIS TIME PLEASE SUBMIT |
| | THE MANUFACTURE SPECS/CUT SHEETS. |
| | PLEASE ALSO SEE THE RISER HAS KEYNOTES NUMBERED UP TO |
| | AND INCLUDING #13 HOWEVER THE RISER KEYNOTES ONLY STATE |
| | NOTES UP TO #11 |
| | PLEASE ADJUST RISER AS NEEDED. |
| | |
| | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 WITH RESPECT |
| | TO LIGHTING CONTROLS ON EACH FLOOR. PLEASE SUBMIT MORE |
| | INFORMATION ON THE PROPOSED LIGHTING CONTROL SYSTEM. |
| | PLEASE SHOW ALL OVER RIDE LOCATIONS FOR THE OCCUPANT TO |
| | SEE THE LIGHTING WHICH IS BEING CONTROLLED OR SHOW A |
| | DETAIL ON THE EXCEPTION TO THIS. |
| | |
| | 6) NOTE: PLEASE SEE 13-415.1.ABC.1.4. THE PLANS CONTAIN |
| | A NOTE FOR OUTSIDE LIGHTING TO BE ROUTED THROUGH AN |
| | ASTRONOMICAL TIME CLOCK HOWEVER PLEASE INDICATE THE |
| | REQUIRED BACK UP FOR PROGRAMMING. THE CODE SECTION |
| | GIVEN REQUIRES A MINIMUM OF 10HRS. THIS MAY BE MORE |
| | HOWEVER AT LEAST 10HRS. |
| | |
| | 7) NOTE: PLEASE SEE 422.13 (2005 NEC) AS STORAGE TYPE |
| | WATER HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD AND |
| | NEEDS TO BE FIGURED AT 125%. PLEASE ADJUST LOAD |
| | CALCULATIONS. |
| | |
| | 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ALL |
| | DEVICES FOR ANY FIRE ALARM SYSTEM. PLANS NEED TO |
| | INDICATE ALL LOCATIONS, HEIGHTS AND THE LEVELS OF THE |
| | DEVICES FOR ADA COMPLIANCE. |
| | |
| | 9) NOTE: PLEASE SEE 250.50, 250.66, 250.53, ETC. THE |
| | SIZE OF THE GROUNDING ELECTRODE CONDUCTOR TO THE FOOTER |
| | STEEL IS REQUIRED TO BE THE SAME SIZE OF THE GROUNDING |
| | ELECTRODE BASED ON THE SERVICE ENTRANCE CONDUCTORS. THE |
| | NOTES ON RISER CONTAIN A 3/0 WHICH IS OK HOWEVER AS THE |
| | SYSTEM IS CONTINUOUS WITH MORE THAN ONE ATTACHMENT THE |
| | SIZE FOR THE FOOTER ALSO NEEDS TO BE 3/0. ONLY WHEN THE |
| | SOLE CONNECTION IS TO THE FOOTER AND NO OTHER |
| | ATTACHMENTS DOES THE CODE PERMIT THE #4 TO BE THE |
| | LARGEST. PLEASE SEE HANDBOOK WHICH SHOWS THE *MINIMUM* |
| | SIZE OF #4. |
| | |
| | 10) NOTE: THE RISER NOTES TO SEE PANELS FOR FEEDERS AND |
| | CONDUIT SIZES HOWEVER THESE FEEDERS ETC AS NOTED ON |
| | EACH PANEL DOES NOT PROVIDE THE EQUIPMENT GROUNDING |
| | CONDUCTORS. PLEASE PROVIDE THE EQUIPMENT GROUNDING |
| | CONDUCTORS. |
| | 250.122, 250.110, ETC |
| | |
| | 11) NOTE: COLOR CODING FOR 277/480V WOULD NEED TO BE |
| | BROWN, PURPLE, YELLOW. THIS COULD BE REDLINED AS THERE |
| | ARE NO 277/480V SYSTEMS ON THE PLANS. IN THE CODE |
| | ORANGE IS FOR HIGH-LEG SYSTEMS. |
| | THIS IS NOTED FOR INFORMATION ONLY. |
| | |
| | 12) NOTE: THE LOAD CALCULATIONS INDICATE THE |
| | REQUIREMENT FOR SHOW WINDOWS HOWEVER PLEASE SEE 220.43B |
| | AND PLEASE SHOW HOW LOAD WAS FIGURED. |
| | |
| | ** IT IS IMPORTANT TO KNOW AS THERE IS SOME INFORMATION |
| | NOT YET SUBMITTED THERE MAY VERY WELL BE NEW COMMENTS |
| | ON THE FOLLOWING REVIEW WHICH COULD NOT BE MADE AT THIS |
| | TIME. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |