Plan Review Notes
Plan Review Notes For Permit 08100686
Permit Number 08100686
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-20 13:25:47BUILDING PLAN REVIEW
 PERMIT: 08100686
 ADD: 3415 S DIXIE HWY
 CONT: R & D CONSTRUCTORS, INC.
 TEL: (561)889-1751
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: TREZISEDESIGN ASSOCIATES, INC.
 STEVEN A. TREZISE
 PHONE (561) 687-4707
 EMAIL: [email protected]
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) IINFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) DISCREPANCY IN PLANS SHEET C1, A4 & A5 INDICATE A
 MIXED USE BUILDING WITH MERCANTILE AND S-1 STORAGE
 WHERE AS THE ELECTRICAL SHEETS E7.1 FIXTURE LEGEND
 INDICATE LIGHTING LFIXTURES AS RETAIL AREAS. PLEASE
 ALSO SEE ELECTRICAL COMMENTS AS FAR AS LIGHTING LOADS
 FOR MERCANTILE USAGE VERSES S-1 STORAGE.SEE ENERGY CODE
 113.400. ALSO NO ENERGY CALCULATIONS WERE PROVIDED AT
 THE TIME OF THIS REVIEW. FROM WHAT I UNDERSSTAND OF
 THIS PROJECT THIS SPACE IS BEING DESIGNED FOR DISPLAY
 AND SALES OF ANTIQUE FURNITURE WHICH WILL FALL UNDER
 THE MERCANTILE OCCUPANCY SEE SECTION 309. INCLUDED
 UNDER THIS HEADING IS WHOLESALE STORES WHERE THE PUBLIC
 ACTUALLY HAS EGRESS TO THE STOCKPILED MERCHANDISE. WHEN
 REVIEWING THE REQUIREMENTS OF A STORAGE S-1 OR S-2
 OCCUPANCY IT IS STRICTLY FOR STORAGE WHERE THE PUBLIC
 IS NOT ALLOWED TO BE IN THE WAREHOUSE AREA. SEE SECTION
 311 FOR STORAGE. PLEASE REVIEW CODE SECTIONS.
  
 3) C1- COVER SHEET PLEASE REVISE OCCUPANT LOADS FOR
 MERCANTILE FIRST FLOOR (30 GROSS) AND SECOND FLOOR (60
 GROSS) SEE TABLE 1004.1.2.
  
 4) SHEET A-4 ELEVATOR MACHINE ROOM INDICATES A WALL
 TYPE (2) NONRATED, PLEASE REFER TO 3006.4 ELEVATOR
 MACHINE ROOMS SHALL NOT HAVE A RATING LEASS THAN THE
 HOISTWAY ENCLOSURE. 1 HR.
  
 5) SHEET A-4 WALL LEGEND ONCE THE OCCUPANCY ISSUES ARE
 CLEARED THE WALL RATINGS WILL ALSO CHANGE TO MOST WALLS
 NOT REQUIRING FIRE RATINGS. SEE DEFINITION OF
 MERCANTILE, 309.
  
 6) SHEET A-4 FIRST FLOOR FINISH FLOOR ELEVATION IN SOME
 AREAS ARE REPRESENTED BY 0'-0" IN OTHER AREAS THERE IS
 A TWO INCH DEPRESSION, PLEASE PROVIDE ADDITIONAL
 INFORMATION IF THIS IS FOR MARBLE FLOORS WITH BED OR IS
 THE FINISH FLOOR IN THESE AREAS ACTUALLY 2INCHES LOWER.
 ADDITIONAL INFORMATION REQUIRED 106.1.2, 11-4.3.7
 SLOPE, 11-4.3.8 CHANGES IN GRADE.
  
 7) SHEET A5 UPPER RECEIVING DOOR# 55 THE PLANS DO NOT
 INDICATE ANY GAURD RAIL SYSTEM WHEN DOOR IS IN THE OPEN
 POSITION, EVEN REMOVABLE. PLEASE SEE 1012.1 THIS
 CONFIGURATION DOES NOT MEET ANY OF THE
 EXCEPTIONS OF LOADING DOCKS OR PIERS.
  
 8) SHEET A6 ROOF PLAN DOES SHOW ROOF DRAINS BUT DOES
 NOT INDICATE ANY SECONDARY DRAINS OR OVERFLOW SCUPPERS.
 PLEASE REVIEW SECTION 1503.4.3 AND THE ACTUAL HEIGHT
 REQUIREMENTS FOR SCUPPERS AND THE AMOUNT OF PONDING
 THAT MAY RESULT FROM THE DISTANCE ROOF DRAINS ARE
 LOCATED FROM THE PARAPETS AND THE PONDING EFFECTS THAT
 MAY OCCUR.
  
 9) 609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
  
 9A) STOREFRONT FIXED GLAZINGARCH NOA 03-1211.08 NOTE
 THIS NOA HAS NOT BEEN REVIEWED TO THE 2004 FBC SEE
 SECTION "C" CALCULATIONS HAVE NOT BEEN REVIEWED TO SEE
 IF 1/3RD INCREASES WERE TAKEN WITH THE FASTENERS.
  
 9B) GLAZED EXTERIOR DOORS ARCH NOA 05-0829.08 NOTE THIS
 NOA HAS NOT BEEN REVIEWED TO THE 2004 FBC SEE SECTION
 "C" CALCULATIONS HAVE NOT BEEN REVIEWED TO SEE IF 1/3RD
 INCREASES WERE TAKEN WITH THE FASTENERS.
  
 9C) SKYLIGHTS
  
 9D) MULLIONS- IF EXCEEDS LENGTHS TESTED AS AN ASSEMBLY
  
 9E) EXTERIOR INSULATED METAL DOORS, SINGLE AND DOUBLE
  
 9F) ROLL UP INSULATED DOOR
  
 9G) ROOF HATCH
  
 9H) WALL LOUVERS- INTAKE GRILLS
  
 9I) ROOFING ASSEMBLIES
  
  
 10) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) S-5 BUILDING ELEVATIONS AND PRESSURE ZONES, SHEET
 S4 INDICATES THIS BUILDING IS DESIGNED AS A "C" COASTAL
 EXPOSURE. PLEASE REVIEW END ZONES OF BUILDING AND
 ASSCIATED PRESSURES ,
 TABLE 1609.6.2.1(4) ADJUSTMENT FACTOR FOR BUILDING
 HEIGHT AND EXPOSURE, THIS BUILDINGS ROOF HEIGHT IS 27'
 WITH A 1.40 FACTOR.
  
 13) NOTE ONE SET OF PLANS THE STRUCTURAL SHEETS ARE NOT
 SIGNED NOR SEALED( ONMJ) ANTONIO ARTHAY PE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 14) NOTE AWNINGS ARE TO BE UNDER A SEPERATE PERMIT.
 INFORMATIONAL ONLY, A LETTER FROM THE OWNER (NOT
 TENANT) IS TO ACCOMPANY ALL FABRIC OR MEMBRANE-COVERED
 STRUCTURE DESIGNED WITH A QUICK REMOVAL OR BREAKAWAY
 MEMBRANE OR FABRIC TO ACKNOWLEDGE THEIR RESPONSIBILITY
 TO HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND
 EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER.
 THE LETTER MUST BE SIGNED BY THE OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  