| Date |
Text |
| 2008-11-04 13:20:10 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES AS ADOPTED |
| | BY FS 553.73 ARE LISTED ON PLANS ACCORDINGLY. FOR |
| | EXAMPLE COVER SHEET INDICATES NFPA-70 ( NATIONAL |
| | ELECTRICAL CODE) AS THE 2002 EDITION. THIS CODE HAS NOT |
| | BEEN IN EFFECT IN THE STATE OF FLORIDA SINCE DECEMBER |
| | 8TH, 2006. |
| | PLANS SHOULD NOTE AS FOLLOWS. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2005 NFPA-70. |
| | |
| | ** SOME OF THESE ARE SHOWN ON ELECTRICAL PLANS HOWEVER |
| | COORDINATION WITH OTHER PLANS IS NEEDED. ELECTRICAL |
| | PLANS DO NOT LIST SPECIFIC ADOPTED CODES |
| | |
| | 3) NOTE: PLEASE INCLUDE NEW LIGHTING CONTROLS FOR NEW |
| | AREAS PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | ** THIS IS FOR NEW INSTALLED ONLY. |
| | ** PLEASE VERIFY CONTROLS AS THE SYMBOL LEGEND CALL FOR |
| | NEW SWITCHES, YET NONE ARE SHOWN AS EXISTING OR NEW. |
| | |
| | 4) NOTE: PLEASE INCLUDE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| | ** NEW BEING INSTALLED. |
| | ** PLEASE BE SURE TO COMPLETE FIXTURE LEGEND WITH |
| | SPECIFIC FIXTURES. |
| | |
| | 5) NOTE: PLEASE BE SURE TO LIST THE REQUIRED LOCATIONS, |
| | LEVELS AND HEIGHTS OF FIRE ALARM DEVICES PER FBC |
| | 11-4.28.1, .2 AND 3. QUOTING ANSI OR OTHER CODES IN |
| | LIEU OF SPECIFIC CODE REQUIRED DETAIL IS NOT PERMITTED. |
| | |
| | ** IT IS IMPORTANT TO KNOW AS THERE IS SOME INFORMATION |
| | NOT YET SUBMITTED THERE MAY VERY WELL BE NEW COMMENTS |
| | ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |