| Notes |
| Date |
Text |
| 2009-09-17 07:38:56 | REVISION TO CHANGE METAL ROOFING PRODUCT APPROVAL IS | | | DENIED. THE ENGLERT SERIES 1300 METAL ROOF WITH FL # | | | 11727.5 HAS A DESIGN UPLIFT PRESSURE OF -60 PSF AND THE | | | PLANS REQUIRE -83.1 PSF IN ROOF ZONE 3. THE PRODUCT | | | LIMITATIONS REQUIRE ANY RATIONAL ANALYSIS COMPUTATIONS | | | TO BE PREPARED BY A QUALIFIED DESIGN PROFESSIONAL IN | | | COMPLIANCE WITH 2007 FBC SECTIONS 104, 105, 106. SEE | | | PAGE 4 OF 7 OF REPORT NO.08-148-1300-90-A3W-ER. SUBMIT | | | SIGNED, SEALED AND DATED CALCULATIONS FOR THIS PRODUCT | | | OR PRODUCT APPROVALS FOR ANOTHER ROOF COVERING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|