2009-09-17 07:38:56REVISION TO CHANGE METAL ROOFING PRODUCT APPROVAL IS
 DENIED. THE ENGLERT SERIES 1300 METAL ROOF WITH FL #
 11727.5 HAS A DESIGN UPLIFT PRESSURE OF -60 PSF AND THE
 PLANS REQUIRE -83.1 PSF IN ROOF ZONE 3. THE PRODUCT
 LIMITATIONS REQUIRE ANY RATIONAL ANALYSIS COMPUTATIONS
 TO BE PREPARED BY A QUALIFIED DESIGN PROFESSIONAL IN
 COMPLIANCE WITH 2007 FBC SECTIONS 104, 105, 106. SEE
 PAGE 4 OF 7 OF REPORT NO.08-148-1300-90-A3W-ER. SUBMIT
 SIGNED, SEALED AND DATED CALCULATIONS FOR THIS PRODUCT
 OR PRODUCT APPROVALS FOR ANOTHER ROOF COVERING.
  