| Plan Review Notes For Permit 08100666 |
| Permit Number |
08100666 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-07-24 16:28:40 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE RISER DIAGRAM INDICATES AN OVERHEAD FEED TO THE | | | ATS. THE RELOCATED METER AND ATS LOCATION SHOWN ON THIS | | | REVISION IS IN VIOLATION OF230.70(A)(1)***READILY | | | ACCESSIBLE LOCATION THE SERVICE DISCONNECTING MEANS | | | SHALL BE INSTALLED AT A READILY ACCESSIBLE LOCATION | | | EITHER OUTSIDE OF A BUILDING OR STRUCTURE OR INSIDE | | | NEAREST THE POINT OF ENTRANCE OF THE SERVICE | | | CONDUCTORS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|