Plan Review Notes
Plan Review Notes For Permit 08100666
Permit Number 08100666
Review Stop E
Sequence Number 2
Notes
Date Text
2009-01-05 11:53:29 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 SHEET E-5:
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. SHEET
 E-5.
  
 2} 702.5 CAPACITY AND RATING
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE ADEQUATE CAPACITY
 AND RATING FOR THE SUPPLY OF ALL EQUIPMENT INTENDED TO
 BE OPERATED AT ONE TIME. OPTIONAL STANDBY SYSTEM
 EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM AVAILABLE
 FAULT CURRENT AT ITS TERMINALS.*** THE OUTPUT OF THE
 GENERATOR IS 125 AMPS, THE CALCULATED LOAD IS 135 AMPS.
 THE GENERATOR IS NOT RATED FOR THIS LOAD. SET A
 SUBPANEL TO SEPARATE THE LOADS OR INCREASE THE
 GENERATOR AMPACITY.
  
 3} THE #6 GROUND RAN TO THE GROUNDING ELECTRODE IS IN
 VIOLATION OF 250.122. THERE MUST BE AN EQUIPMENT GROUND
 FROM THE PANEL, WHERE THE SHORT WILL BE DETECTED, TO
 THE GENERATOR TO ENABLE THE MAIN TO TRIP UNDER A SHORT
 CIRCUIT CONDITION.THE NEUTRAL, TO WHICH THE GENERATOR
 "GROUND" IS CONNECTED THROUGH THE GEC, AND THE GROUND
 WILL BE ISOLATED AFTER THE FIRST MEANS OF DISCONNECT
 PER 210.24(A)(5), WHICH WILL BE THE ATS AS CONFIGURED
 ON THE RISER DIAGRAM.
  
 4} PROVIDE THE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR AND THE TRANSFER SWITCH. NOTE: THE TRANSFER
 SWITCH MUST HAVE AN "OFF" POSITION AS THE FIRST MEANS
 OF DISCONNECT, AND MUST BE 200 AMP RATED WITH AN AIC
 RATING CONCURRENT WITH THE SERVICE EQUIPMENT AND
 GREATER THAN THE FAULT CURRENT CALCULATION. SEE COMMENT
 #1.
  
 5} CIRCUITS #9 & 11 @ 3000 VA ARE IN VIOLATION OF
 310.16 & 210.23(A)(1)- "CORD-AND-PLUG-CONNECTED
 EQUIPMENT NOT FASTENED IN PLACE THE RATING OF ANY ONE
 CORD-AND-PLUG-CONNECTED UTILIZATION EQUIPMENT NOT
 FASTENED IN PLACE SHALL NOT EXCEED 80 PERCENT OF THE
 BRANCH-CIRCUIT AMPERE RATING". 3000/120=25 AMPS.
  
 6} CIRCUITS 3O, 32 ,34, 36 FOR THE CONDENSING UNITS
 HAVE INCORRECT OVERCURRENT PROTECTION PER MANUFACTURERS
 SPECIFICATIONS GIVEN ON SHEET M-5. 110.3(B).
  
 7} CIRCUIT #10 INDICATES THE DISHWASHER/DISPOSER ON THE
 SAME CIRCUIT IN VIOLATION OF 210.23(A)(1).
  
 NOTE: THE SMOKE DETECTOR CIRCUIT # 24 MUST BE ON AN ARC
 FAULT BREAKER PER 210.12(B).
  
 SHEET E-3:
  
 8} 9B-3.0472 CARBON MONOXIDE PROTECTION. (2) EVERY
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES***ALTHOUGH THE DETECTOR IN
 THE GARAGE IS RECOMMENDED AND PERMISSIBLE, THE
 REQUIREMENT IS FOR THE HALLWAYS OUTSIDE SLEEPING ROOMS.
  
 9} 680.43(A)(3) PROTECTION, SPA OR HOT TUB SUPPLY
 RECEPTACLES THAT PROVIDE POWER FOR A SPA OR HOT TUB
 SHALL BE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTED.***
 INDICATE ON PLANS.
  
 SHEET E-4:
  
 10} 210.52(D) BATHROOMS IN DWELLING UNITS, AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS
 WITHIN 900 MM (3 FT) OF THE OUTSIDE EDGE OF EACH BASIN.
 THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP.***BATH #2 DOES NOT COMPLY WITH REQUIRED
 SPACING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  