Plan Review Notes
Plan Review Notes For Permit 08100666
Permit Number 08100666
Review Stop B
Sequence Number 2
Notes
Date Text
2009-01-26 13:52:262004 FBC W/2007 REVISIONS
 ADDITION AND LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. FS 713
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 3) THE DETAILS FOR THE CUPOLA ARE INCOMPLETE. PLEASE
 SPECIFY THE DIMENSIONS, THE ROOF FRAMING, ROOF
 SHEATHING, ROOF TO WALL CONNECTIONS, ETC.
  
 4) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 CAST-CRETE LINTELS DOES NOT INCLUDE THE 8" WIDE LINTELS
 WHICH ARE FOR THE 8" BLOCK WALLS. PLEASE SUBMIT THE NOA
 FOR 8" WIDE LINTELS. DCA RULE 9B-72
  
 5) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 TAMKO MODIFIED ROOF COVERING IS FOR INSTALLATION ON
 CONCRETE DECKS. THE FLAT ROOF OVER THE LOGGIA IS A WOOD
 DECK. PLEASE SUBMIT THE NOA FOR WOOD DECKS. SPECIFY THE
 ASSEMBLY, FASTENING OPTION AND DESIGN PRESSURE THAT
 WILL BE USED. IF ENHANCED FASTENING AT CORNER AND
 PERIMETER AREAS IS REQUIRED, SUBMIT RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 OF THE
 NOA.
  
 NOTE: THE LETTER THAT WAS SUBMITTED IN RESPONSE TO THE
 COMMENTS CONTAINED SEVERAL ERRORS AS TO THE SHEETS OF
 THE PLANS WHERE THE CORRECTIONS WERE MADE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW