2008-11-19 09:03:39DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P-1 SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH
 DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN
 DIAMETER. SECTION 406.3.
  
 2. SHT P-1 SANITARY RISER DIAGRAM. THE CLEANOUT BEHIND
 THE W/M SHALL BE INSTALLED A MINIMUM 4 FEET ABOVE
 FINISHED FLOOR FOR ACCESS. SECTION 708.9
  
 3. SHT P-1 FLOOR PLAN AND SANITARY RISER DIAGRAM.
 PLEASE SHOW THE CLEANOUTS REQUIRED BY SECTIONS 708.3.4
 & 708.3.5, AT THE BASE OF EACH STACK AND NEAR THE
 JUNCTION OF THE BUILDING DRAINS AND THE BUILDING SEWER.
  
 4. SHT P-2 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 ARE REQUIRED ON THE SUPPLY LINES TO THE DISHWASHER AND
 THE ICE MAKER IN THE KITCHEN AREA. SECTION 604.9.
  
 5. SHT P-2 WATER RISER DIAGRAM. THE RELIEF VALVE
 DISCHARGE FOR THE WATER HEATER SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHALL HAVE A VISIBLE AIR GAP OR
 AIR GAP FITTING LOCATED IN THE SAME ROOM AS THE WATER
 HEATER. SECTION 504.6.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  