| Date |
Text |
| 2008-11-19 09:03:39 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | 1. SHT P-1 SANITARY RISER DIAGRAM. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH |
| | DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN |
| | DIAMETER. SECTION 406.3. |
| | |
| | 2. SHT P-1 SANITARY RISER DIAGRAM. THE CLEANOUT BEHIND |
| | THE W/M SHALL BE INSTALLED A MINIMUM 4 FEET ABOVE |
| | FINISHED FLOOR FOR ACCESS. SECTION 708.9 |
| | |
| | 3. SHT P-1 FLOOR PLAN AND SANITARY RISER DIAGRAM. |
| | PLEASE SHOW THE CLEANOUTS REQUIRED BY SECTIONS 708.3.4 |
| | & 708.3.5, AT THE BASE OF EACH STACK AND NEAR THE |
| | JUNCTION OF THE BUILDING DRAINS AND THE BUILDING SEWER. |
| | |
| | 4. SHT P-2 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS |
| | ARE REQUIRED ON THE SUPPLY LINES TO THE DISHWASHER AND |
| | THE ICE MAKER IN THE KITCHEN AREA. SECTION 604.9. |
| | |
| | 5. SHT P-2 WATER RISER DIAGRAM. THE RELIEF VALVE |
| | DISCHARGE FOR THE WATER HEATER SHALL NOT HAVE ANY |
| | TRAPPED SECTIONS AND SHALL HAVE A VISIBLE AIR GAP OR |
| | AIR GAP FITTING LOCATED IN THE SAME ROOM AS THE WATER |
| | HEATER. SECTION 504.6.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |