| 2008-11-04 14:31:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | |
| | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE |
| | 2004 FBC 13-600.3.A (12-8-06 REVISION). |
| | |
| | 2) ENERGY CALCULATIONS LINE 6 NEEDS TO SHOW THE TOTAL |
| | SQUARE FEET UNDER AIR FOR THE HOUSE, SEE 2004 FBC |
| | 13-600.0 METHOD A AND 13-600.2.A.3.2. |
| | |
| | 3) ENERGY CALCULATIONS LINE 8A SHOWS R-6 ON SLABS EDGE, |
| | PLANS SHOW NO INSULATION ON SLABS EDGE. THE TWO MUST |
| | COINCIDE, PLEASE CORRECT SEE 2004 FBC 13-605.1.ABC.1.2. |
| | |
| | 4) ENERGY CALCULATIONS LINE 9A SHOWS R-11 ON CONCRETE |
| | WALLS, PLANS SHOW R-4.1 ON THE CONCRETE WALLS. THE TWO |
| | MUST COINCIDE, PLEASE CORRECT PER 2004 FBC 13-103.3. |
| | |
| | 5) ENERGY CALCULATIONS LINE 10A SHOWS UNDER ATTIC, |
| | PLANS SHOW ICYNENE BEING INSTALLED UNDER THE ROOF THIS |
| | WOULD BE A SINGLE ASSEMBLY, PLEASE CORRECT SEE 2004 FBC |
| | 13-604.2.A.1. |
| | |
| | 6) ENERGY CALCULATIONS LINE 12A SHOWS A 60,000 BTU A/C |
| | SYSTEM IS BEING INSTALLED, MECHANICAL PLANS SHOW THREE |
| | SYSTEM BEING INSTALLED ONE 3.5 TON AND TWO 2 TON |
| | SYSTEMS, PLEASE CORRECT PER 2004 FBC-103.3. DO SAME FOR |
| | LINE 13A HEATING SYSTEMS. |
| | |
| | 7) ENERGY CALCULATIONS LINE 14C IS TAKING THE CREDIT |
| | FOR H.R.U. (HEAT RECOVERY UNIT). PLEASE SUBMIT DETAILED |
| | MANUFACTURER'S SPECIFICATION'S FOR THE UNIT AND SHOW |
| | WERE THE UNIT WILL BE INSTALLED ON THE MECHANICAL PLAN. |
| | SEE 2004 FBC 13-612.2.A.3.1. |
| | |
| | 8) THE COOLING LOAD CALCULATIONS SUBMITTED ARE ONLY FOR |
| | ONE ZONE. PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR |
| | ALL THREE ZONES, PER 2004 FBC 13-607.1.ABC.1. |
| | |
| | 9) MECHANICAL PLAN M-1 SHOWS THE CONDENSATE LINE FROM |
| | A.H.U. #1 DISCHARGING ON THE FRONT PORCH. THE |
| | CONDENSATE WATER MAY NOT DISCHARGE THERE, PLEASE |
| | CORRECT PER 2004 FBC/R M1411.3. |
| | |
| | 10) A/C SYSTEM MODEL NUMBERS AHU TWE040E CU TWX042D100A |
| | AND AHU TWE031E CU TWX024C100A LISTED ON THE A/C |
| | EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI |
| | DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI |
| | CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |