2008-11-04 14:31:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) ENERGY CALCULATIONS LINE 6 NEEDS TO SHOW THE TOTAL
 SQUARE FEET UNDER AIR FOR THE HOUSE, SEE 2004 FBC
 13-600.0 METHOD A AND 13-600.2.A.3.2.
  
 3) ENERGY CALCULATIONS LINE 8A SHOWS R-6 ON SLABS EDGE,
 PLANS SHOW NO INSULATION ON SLABS EDGE. THE TWO MUST
 COINCIDE, PLEASE CORRECT SEE 2004 FBC 13-605.1.ABC.1.2.
  
 4) ENERGY CALCULATIONS LINE 9A SHOWS R-11 ON CONCRETE
 WALLS, PLANS SHOW R-4.1 ON THE CONCRETE WALLS. THE TWO
 MUST COINCIDE, PLEASE CORRECT PER 2004 FBC 13-103.3.
  
 5) ENERGY CALCULATIONS LINE 10A SHOWS UNDER ATTIC,
 PLANS SHOW ICYNENE BEING INSTALLED UNDER THE ROOF THIS
 WOULD BE A SINGLE ASSEMBLY, PLEASE CORRECT SEE 2004 FBC
 13-604.2.A.1.
  
 6) ENERGY CALCULATIONS LINE 12A SHOWS A 60,000 BTU A/C
 SYSTEM IS BEING INSTALLED, MECHANICAL PLANS SHOW THREE
 SYSTEM BEING INSTALLED ONE 3.5 TON AND TWO 2 TON
 SYSTEMS, PLEASE CORRECT PER 2004 FBC-103.3. DO SAME FOR
 LINE 13A HEATING SYSTEMS.
  
 7) ENERGY CALCULATIONS LINE 14C IS TAKING THE CREDIT
 FOR H.R.U. (HEAT RECOVERY UNIT). PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S FOR THE UNIT AND SHOW
 WERE THE UNIT WILL BE INSTALLED ON THE MECHANICAL PLAN.
 SEE 2004 FBC 13-612.2.A.3.1.
  
 8) THE COOLING LOAD CALCULATIONS SUBMITTED ARE ONLY FOR
 ONE ZONE. PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR
 ALL THREE ZONES, PER 2004 FBC 13-607.1.ABC.1.
  
 9) MECHANICAL PLAN M-1 SHOWS THE CONDENSATE LINE FROM
 A.H.U. #1 DISCHARGING ON THE FRONT PORCH. THE
 CONDENSATE WATER MAY NOT DISCHARGE THERE, PLEASE
 CORRECT PER 2004 FBC/R M1411.3.
  
 10) A/C SYSTEM MODEL NUMBERS AHU TWE040E CU TWX042D100A
 AND AHU TWE031E CU TWX024C100A LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  