| 2008-11-14 14:24:40 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE GENERATOR SHOWN ON THE RISER DIAGRAM MUST BE |
| | LABELED AS FUTURE OR PROVIDE ALL DOCUMENTATION REQUIRED |
| | FOR A RESIDENTIAL GENERATOR INSTALLATION WITH THE |
| | RESUBMITTAL. |
| | |
| | 2} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED |
| | FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER |
| | 250.118, SIZED PER 250.122. |
| | |
| | 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED |
| | FROM THE TRANSFER SWITCH TO THE GENERATOR PER 250.122. |
| | |
| | 4} PANEL "A" IS LISTED AS HAVING A 225 AMP MAIN |
| | BREAKER, BUT HAS A 200 AMP MAIN DISCONNECT FEEDING IT. |
| | IT IS ALSO SHOWN AS BEING RECESSED , VERIFY THESE AS A |
| | REVISION WOULD BE REQUIRED AT A LATER DATE NOT CORRECT. |
| | |
| | 5} THE A/C EQUIPMENT PANEL DESIGNATION AND CIRCUIT |
| | NUMBERS ARE SHOWN IN PANEL "A" BUT LISTED IN PANEL "E". |
| | CORRELATE SAME, 408.4 |
| | |
| | 6} 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO |
| | THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS |
| | OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT |
| | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | EXCEPTION: WHERE THE 20-AMPERE CIRCUIT SUPPLIES A |
| | SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE |
| | SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED IN |
| | ACCORDANCE WITH 210.23(A)(1) AND (A)(2)***CIRCUIT A-30 |
| | IN THE POWDER ROOM AND OFFICE BATHROOM, SHEET E-1, AND |
| | THE NEW BATH VIOLATE THE EXCEPTION AS THE LIGHT AND FAN |
| | ARE ON THAT CIRCUIT |
| | |
| | 7} ANOTHER RECEPTACLE MUST BE ADDED IN THE NEW |
| | BATHROOM, SHEET E-2, TO COMPLY WITH 210.52(D). |
| | |
| | 8} A SMOKE ALARM MUST BE ADDED OUTSIDE THE EXISTING |
| | BEDROOM ON SHEET E-1TO COMPLY WITH R313.1.2 "OUTSIDE |
| | EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE BEDROOMS".. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |