| 2008-11-18 10:25:59 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ALTERATIONS AND ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) ON SHEET A1 THE WALL TYPE SPECIFIED FOR THE NEW |
| | POWDER ROOM #114 IS INCORRECT. DRYWALL IS SPECIFIED ON |
| | THE EXTERIOR WALLS. PLEASE CORRECT. |
| | |
| | 4) THE MASONRY OPENING SIZES SPECIFIED FOR THE OVERHEAD |
| | GARAGE DOORS IN THE DOOR SCHEDULE ON A6 ARE INCORRECT. |
| | PLEASE REVISE. |
| | |
| | 5) SUBMIT PRODUCT APPROVALS OR DESIGN DETAILS FOR THE |
| | ROOF CUPOLA. RULE 9B-72 AND FBC R801.2 |
| | |
| | 6) SHOW COMPLIANCE WITH R309.1 OPENING PROTECTION. |
| | OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE |
| | EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1-3/8 |
| | INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE |
| | STEEL DOORS NOT LESS THAN 1-3/8 INCHES (35 MM) THICK, |
| | OR 20-MINUTE FIRE-RATED DOORS. |
| | |
| | 7) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR |
| | THE 2 X 8 RAFTERS TO THE EXISTING TRUSSES AT THE NEW |
| | FRONT PORCH ROOF. FBC R801.2 |
| | |
| | 8) THE TRUSS ANCHOR NUMBERS IN THE SCHEDULE ON S4 DO |
| | NOT CORRESPOND TO THE ID TAGS ON THE ROOF FRAMING |
| | PLANS. PLEASE CLARIFY. FBC 106.1.1 AND R802.1.6.5 |
| | |
| | 9) ON S2 THE DESIGN CRITERIA SPECIFIES THE 2002 FBC AND |
| | ASCE 7-98. PLEASE UPDATE TO 2004 FBC AND ASCE 7-02. SEE |
| | FBC R CHAPTER 43. |
| | |
| | 10) THE STRUCTURAL NOTES, WIND-LOADING NOTES AND TRUSS |
| | NOTES ON SHEET S5 SPECIFY ASCE 7-98. PLEASE CORRECT TO |
| | ASCE 7-02. FBC R CHAPTER 43. |
| | |
| | 11) PROVIDE A WINDOW BUCK DETAIL. FBC R613.6.1.1 |
| | |
| | 12) SHOW COMPLIANCE OF STAIRS WITH R311.5.3.2 TREAD |
| | DEPTH. THE MINIMUM TREAD DEPTH, EXCLUSIVE OF NOSING, |
| | SHALL BE NOT LESS THAN 9 INCHES.TREADS AND RISERS OF |
| | STAIRS SHALL BE PERMITTED TO BE SO PROPORTIONED THAT |
| | THE SUM OF TWO RISERS AND A TREAD, EXCLUSIVE OF |
| | PROJECTION OF NOSING, IS NOT LESS THAN 24 INCHES NOR |
| | MORE THAN 25 INCHES. THE TREAD DEPTH SHALL BE MEASURED |
| | HORIZONTALLY BETWEEN THE VERTICAL PLANES OF THE |
| | FOREMOST PROJECTION OF ADJACENT TREADS AND AT A RIGHT |
| | ANGLE TO THE TREAD'S LEADING EDGE. THE GREATEST TREAD |
| | DEPTH WITHIN ANY FLIGHT OF STAIRS SHALL NOT EXCEED THE |
| | SMALLEST BY MORE THAN 3/8 INCH. |
| | |
| | 13) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 14) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | GLASS BLOCK. FAC RULE 9B-72 |
| | |
| | 15) NOA NO. 01-0209.03 FOR THE CAST-CRETE LINTELS |
| | SPECIFIED ON SHEET S1, IS EXPIRED. PLEASE CORRECT. FAC |
| | RULE 9B-72 |
| | |
| | 16) SPECIFY WHICH ATTACHMENT METHOD LISTED IN THE |
| | PRODUCT APPROVAL NOA WILL BE USED TO ANCHOR THE |
| | CONCRETE ROOF TILES. FBC R905.3.7 |
| | |
| | 17) PRODUCT APPROVALS WERE SUBMITTED FOR PGT HORIZONTAL |
| | ROLLER WINDOWS, HOWEVER, ON SHEET A6 ALL WINDOWS ARE |
| | SPECIFIED AS CASEMENT. PLEASE INDICATE WHICH WINDOWS |
| | WILL BE HORIZONTAL ROLLER WINDOWS OR REMOVE THESE |
| | PRODUCT APPROVALS FROM THE PACKAGE. RULE 9B-72 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |