| Plan Review Notes For Permit 08100660 |
| Permit Number |
08100660 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-02-04 10:30:08 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE ADDRESS ON THE PLAN DOES NOT MATCH THE ADDRESS | | | ON THE APPLICATION, CORRELATE SAME. 106.1 FBC | | | | | | 2} THE PLAN SUBMITTED DOES NOT SEEM TO BE THE SAME PLAN | | | AS WAS SUBMITTED 11/14/08 AS THE COMMENTS MADE DO NOT | | | RELATE TO THIS PLAN.SEE COMMENT #1. | | | | | | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON A SITE OR | | | FLOOR PLAN, METER ENCLOSURE, DISCONNECTS AND PANELS, SO | | | THAT COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE | | | REVIEWED. A DISCONNECT MAY BE REQUIRED PER | | | 230.70(A)(1). | | | | | | 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.*** THIS | | | COMMENT IS MADE BECAUSE THE NEW PANEL WITH WOULD BE | | | SUBJECT TO LINE FAULT CURRENT AS THE FIRST MEANS OF | | | DISCONNECT. | | | | | | 5} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE | | | EQUIPMENT TO BE INSTALLED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|