| 2008-11-18 08:43:03 | |
| | |
| | |
| | ** FAILED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE INDICATE THE LOCATION OF THE PANEL. |
| | 110.26,240.24, 408.36 |
| | |
| | 2) NOTE: PLANS SUBMITTED CONTAIN A TITLE BLOCK FROM AN |
| | ENGINEERING FIRM. PLANS MUST BE SIGNED, DATED AND |
| | SEALED FORM THAT ENGINEERING FIRM PER FS 471.025, FAC |
| | 61G15-23.002. |
| | |
| | 3) NOTE: MISSING EQUIPMENT GROUNDING AFTER THE FIRST |
| | MEANS OF DISCONNECT PER 250.110,250.122. |
| | |
| | 4) NOTE: NEEDS TO HAVE TWO GROUND RODS. 250.50, 250.56 |
| | |
| | 5) NOTE: RISER INDICATES AN OVER HEAD SERVICE HOWEVER |
| | THE NOTE ON RISER MENTIONS TO BASE OF POLE WHICH WOULD |
| | LEND TO AN UNDERGROUND SERVICE. |
| | PLEASE COORDINATE WHICH ONE IT WILL BE AND REVISE AS |
| | NEEDED. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |