Plan Review Notes
Plan Review Notes For Permit 08100615
Permit Number 08100615
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-05 13:39:13 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SERVICE ON SHEET 3.1 IS SHOWN AS AN EXISTING BUT
 MUST BE CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE
 IS A GROUNDING ELECTRODE CONDUCTOR AT THE METER AND A
 GROUNDING ELECTRODE SYSTEM SHOWN AT THE PANEL WITH A
 DISCONNECT IN BETWEEN THE TWO IN VIOLATION OF
 250.24(A)(5)" LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE."
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225, 240 AND 230 CAN BE
 REVIEWED.
  
 3} INDICATE HOW THE EQUIPMENT GROUND IS RAN AND WHERE
 IT ORIGINATES, ON THE SERVICE RISER DIAGRAM SEE COMMENT
 #1
  
 4} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE NOTE #2 TO REFLECT THIS
 CHANGE.
  
 5} ELECTRICAL NOTE #3 IS INCORRECT REGARDING GFCI
 PROTECTION AT THE SINK***210.8(A) DWELLING UNITS ALL
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL. (6) KITCHENS ? WHERE THE RECEPTACLES ARE
 INSTALLED TO SERVE THE COUNTERTOP SURFACES. PLEASE
 CORRECT.
  
 6} ELECTRICAL NOTE #4 REGARDING THE CIRCUITING FOR
 SMOKE ALARMS IS NOT A VIOLATION BUT IT SHOULD BE NOTED
 THAT THE CIRCUIT MUST COMPLY WITH 210.12 AND BE AFCI
 PROTECTED. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS
 INDICATE THE LOCATIONS OF THE SOUNDING DEVICES.
  
 7} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE
 THE ALARMS ON THE PLAN TO INDICATE COMPLIANCE.
  
 8} NOTE #7 REFERENCES ARTICLE 310.17(A) WHICH IS NOT IN
 THE 2005 NEC, SEE COMMENT #4. THE REFERENCES TO
 210.52(A) AND 210.52(E) ARE FOR OUTLETS, NOT "J" BOXES.
 CORRECT NOTES TO REFERENCE CURRENT CODES.
  
 9} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 10} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER