Plan Review Notes
Plan Review Notes For Permit 08100614
Permit Number 08100614
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-01 09:37:34 
  
 DENIED
  
 1) PROVIDE CORRECT DESIGN PRESSURES ON THE SHUTTER
 SCHEDULE FOR THE AREA OF OPENING AND ZONE THE OPENING
 IS IN, IF YOU USE THE WORST CASE FOR ALL OPENINGS AS
 CHOSEN ON THE ENGINEERING SHEET (-122.3) OR AS MARKED
 ON SHUTTER SCHEDULE (-116.1)? SOME CONNECTIONS WILL NOT
 MEET THE REQUIRED PRESSURES.
  
 2) PROVIDE THE TOP AND BOTTOM CONNECTION ON THE
 SCHEDULE (A/D) FOR SHUTTERS 1 THRU 7 AND (G/H) FOR
 NUMBER 8
  
 3) THE EDGE DISTANCE THAT WAS CHOSEN (2") IS SUBJECT TO
 A REDUCTION IN ON CENTER SPACING (SEE TABLE ON SHEET
 14), O/C SPACING X .50 THIS WOULD BRING THE ON CENTER
 SPACING BELOW THE MINIMUM OF 3". THIS CAN BE RECTIFIED
 BY USING THE CORRECT DESIGN PRESSURE OR INCREASING THE
 EDGE DISTANCE TO 3 1/2" TO USE THE SPACINGS FROM THE
 TABLES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  