| Plan Review Notes For Permit 08100614 |
| Permit Number |
08100614 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-01 09:37:34 | | | | | | | DENIED | | | | | | 1) PROVIDE CORRECT DESIGN PRESSURES ON THE SHUTTER | | | SCHEDULE FOR THE AREA OF OPENING AND ZONE THE OPENING | | | IS IN, IF YOU USE THE WORST CASE FOR ALL OPENINGS AS | | | CHOSEN ON THE ENGINEERING SHEET (-122.3) OR AS MARKED | | | ON SHUTTER SCHEDULE (-116.1)? SOME CONNECTIONS WILL NOT | | | MEET THE REQUIRED PRESSURES. | | | | | | 2) PROVIDE THE TOP AND BOTTOM CONNECTION ON THE | | | SCHEDULE (A/D) FOR SHUTTERS 1 THRU 7 AND (G/H) FOR | | | NUMBER 8 | | | | | | 3) THE EDGE DISTANCE THAT WAS CHOSEN (2") IS SUBJECT TO | | | A REDUCTION IN ON CENTER SPACING (SEE TABLE ON SHEET | | | 14), O/C SPACING X .50 THIS WOULD BRING THE ON CENTER | | | SPACING BELOW THE MINIMUM OF 3". THIS CAN BE RECTIFIED | | | BY USING THE CORRECT DESIGN PRESSURE OR INCREASING THE | | | EDGE DISTANCE TO 3 1/2" TO USE THE SPACINGS FROM THE | | | TABLES | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|