| Plan Review Notes For Permit 08100612 |
| Permit Number |
08100612 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-04 13:35:57 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} ARTICLE 471.003 UNDER EXEMPTIONS STATES. " REQUIRES | | | AN AGGREGATE SERVICE CAPACITY OF 600 AMPERES (240 | | | VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM OR | | | 800 AMPERES (240 VOLTS) OR LESS ON A COMMERCIAL OR | | | INDUSTRIAL ELECTRICAL SYSTEM; ". THIS SYSTEM THEREFORE | | | REQUIRES ENGINEERING IF OVER 240 VOLTS AND MUST BE | | | SIGNED, SEALED AND DATED PER 471.025.NOTE THE VOLTAGE | | | IS NOT STATED ON THE PLAN.INCLUDE VOLTAGES ON THE PLAN, | | | PRIMARY AND SECONDARY. | | | | | | 2} IF THIS SYSTEM IS 240 VOLTS OR LESS THE PERSON | | | TAKING RESPONSIBILITY FOR THE DESIGN MUST PRINT AND | | | SIGN THEIR NAME TO SAME, ALL SHEETS, PER 106.1. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | |
|