 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} ARTICLE 471.003 UNDER EXEMPTIONS STATES. " REQUIRES
 AN AGGREGATE SERVICE CAPACITY OF 600 AMPERES (240
 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM OR
 800 AMPERES (240 VOLTS) OR LESS ON A COMMERCIAL OR
 INDUSTRIAL ELECTRICAL SYSTEM; ". THIS SYSTEM THEREFORE
 REQUIRES ENGINEERING IF OVER 240 VOLTS AND MUST BE
 SIGNED, SEALED AND DATED PER 471.025.NOTE THE VOLTAGE
 IS NOT STATED ON THE PLAN.INCLUDE VOLTAGES ON THE PLAN,
 PRIMARY AND SECONDARY.
  
 2} IF THIS SYSTEM IS 240 VOLTS OR LESS THE PERSON
 TAKING RESPONSIBILITY FOR THE DESIGN MUST PRINT AND
 SIGN THEIR NAME TO SAME, ALL SHEETS, PER 106.1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  