| 2008-11-04 09:59:16 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE TITLE BLOCK IS INDICATING |
| | APPLIED DESIGN INITIATIVE LLC WHICH IS REQUIRED TO BE |
| | LICENSED IN THE STATE O FLORIDA PER FLORIDA STATUTES |
| | 481.219. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 WHICH REQUIRES LICENSE NUMBER TO BE LISTED |
| | ON TITLE BLOCKS. IF THE WORK IS SOLELY THROUGH THE |
| | RESPONSIBLE ARCHITECT AS LISTED PLEASE EITHER INCLUDE |
| | LICENSING OR REMOVE FROM TITLE BLOCKS. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADE |
| | WHICH INDICATE THIS INFORMATION. |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES AS ADOPTED |
| | BY FS 553.73 ARE LISTED ON PLANS ACCORDINGLY. FOR |
| | EXAMPLE COVER SHEET INDICATES NFPA-70 ( NATIONAL |
| | ELECTRICAL CODE) AS THE 2002 EDITION. THIS CODE HAS NOT |
| | BEEN IN EFFECT IN THE STATE OF FLORIDA SINCE DECEMBER |
| | 8TH, 2006. |
| | PLANS SHOULD NOTE AS FOLLOWS. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2005 NFPA-70. |
| | |
| | ** SOME OF THESE ARE SHOWN ON ELECTRICAL PLANS HOWEVER |
| | COORDINATION WITH OTHER PLANS IS NEEDED. |
| | |
| | 3) NOTE: PLEASE LIST THE MAXIMUM TIMES ON OCCUPANCY |
| | SENSORS/OVER RIDES AS NOTED ON SYMBOL LEGEND. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |