Plan Review Notes
Plan Review Notes For Permit 08100562
Permit Number 08100562
Review Stop B
Sequence Number 2
Notes
Date Text
2009-01-14 08:09:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE TYPICAL SHORING PLAN PREPARED BY CBI CONSULTING
 INC. DOCUMENTS SUBMITTED FOR PUBLIC RECORD ARE TO BE IN
 ACCORDANCE WITH FAC61G15-23.002, TITLE BLOCK. PLEASE
 REVISE.
  
 2. SHORING DETAILS ARE DESIGNED TO FBC2007. THIS IS NOT
 GOVERNING CODE. PLEASE REVISE.
  
 3. SHORING DETAILS ARE DESIGNED TO ACI318-05, STANDARD
 IN EFFECT IS 02 VERSION. PLEASE REVISE TO INCLUDE 02,
 SEE FBC CHAPTER 35. PLEASE CHECK ALL STANDARDS.
  
 4. IT IS NOT CLEAR WHY FIVE SETS OF SHORING DRAWINGS
 WERE SUBMITTED BUT SIX SETS OF SPECS WERE SUBMITTED.
 PLEASE REMOVE UNNECESSARY SETS. TWO SETS ARE REQUIRED.
 IF THE CONTRACTOR REQUIRES ADDITIONAL STAMPED SETS,
 PLEASE SUBMIT COMPLETE SETS OR SUBMIT A REQUEST FOR
 PARTIAL STAMPED SETS. OTHERWISE, ONLY TWO COMPLETE SETS
 WILL BE RETURNED STAMPED TO THE CONTRACTOR.
  
 5. ENGINEER'S REPORTS WILL BE REQUIRED. PLEASE SUBMIT
 EITHER TO THE CITY INSPECTOR OR THROUGH PLAN REVIEW.
 (INFORMATIONAL ONLY.)
  
 6. THE ENGINEER'S REPAIR MANUAL IS NOT A PART OF THE
 PERMIT PACKAGE. PLEASE SUBMIT, IF AVAILABLE.
  
 7. SEE SHEET S5. FOR COLUMN/TEE REPAIRS, NOTE 1 STATES
 THAT PRIOR TO REPAIRS, TEE BEAM SHALL BE FULLY SHORED
 TO GROUND LEVEL. IT APPEARS THAT REPAIR WORK HAS
 COMMENCED, BUT NO SHORING HAS BEEN PROVIDED. SEE ALSO
 S5, SHORING BRACING AND SUPPORT, STAES THAT SHORING,
 BRACING OR SUPPORT SHALL BE PROVIDED.
  
 8. SEE NOTE SHORING BRACING AND SUPPORT, SHEET S5, ITEM
 3. PLEASE PROVIDE A SHORING PLAN AS REQUIRED. SHORING
 DETAILS WERE PROVIDED BUT NO INFORMATION REGARDING
 LOCATIONS REQUIRED. ACCORDING TO THE PLAN, IT APPEARS
 THAT SHORING IS REQUIRED IN ALL LOCATIONS OF REPAIR
 UNLESS THE REPAIR IS A COLUMN SPALL, SEE SHEET S5.
 OTHER SPALLS REQUIRE SHORING, ACCORDING TO THE PLAN. IS
 THIS FURTHER CLARIFIED IN THE REPAIR MANUAL WHICH WAS
 NOT SUBMITTED?
  
 9. I HAVE BEEN ADVISED BY THE CITY INSPECTOR THAT
 MASTERBUILDER PRODUCTS ARE ON THE JOBSITE, BUT THE
 SPECIFICATIONS PROVIDED ARE FOR SIKA. THIS COMMENT IS
 ADVISORY ONLY; PLEASE BE AWARE THAT NO SUBSTITUTIONS
 ARE PERMITTED UNLESS APPROVED BY THE ENGINEER OF RECORD
 PRIOR TO INSTALLATION/APPLICATION.
  
  