Plan Review Notes
Plan Review Notes For Permit 08100556
Permit Number 08100556
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-11-12 13:51:08***DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 101, 2003 AND NFPA 30,
 STANDARD FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS. PLEASE
 ADD TO DRAWINGS.
  
 2) CLEARLY ILLUSRATE LOCATION OF TANK AND EXHAUST
 TERMINUS AS IT RELATES TO BUILDING OPENINGS AND MEANS
 OF EGRESS.
  
 3) PROVIDE INFORMTION REGARDING ROOM CONSTRUCTION AND
 ANY WALL FIRE RATING INFORMATION.
  
 4) PROVIDE MANUFACTURER SPECIFICATION SHEETS AND
 PRODUCT APPROVALS FOR FUEL TANK.
  
 5) PROVIDE APPLICABLE SIGNAGE IN ACCORDANCE WITH NFPA
 704.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756