| Plan Review Notes For Permit 08100556 |
| Permit Number |
08100556 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-12 13:51:08 | ***DENIED*** | | | | | | 1) WORK SHALL COMPLY WITH NFPA 101, 2003 AND NFPA 30, | | | STANDARD FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS. PLEASE | | | ADD TO DRAWINGS. | | | | | | 2) CLEARLY ILLUSRATE LOCATION OF TANK AND EXHAUST | | | TERMINUS AS IT RELATES TO BUILDING OPENINGS AND MEANS | | | OF EGRESS. | | | | | | 3) PROVIDE INFORMTION REGARDING ROOM CONSTRUCTION AND | | | ANY WALL FIRE RATING INFORMATION. | | | | | | 4) PROVIDE MANUFACTURER SPECIFICATION SHEETS AND | | | PRODUCT APPROVALS FOR FUEL TANK. | | | | | | 5) PROVIDE APPLICABLE SIGNAGE IN ACCORDANCE WITH NFPA | | | 704. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | 2008-10-27 10:12:54 | TO "M" BOX |
|