Plan Review Notes
Plan Review Notes For Permit 08100556
Permit Number 08100556
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-20 16:54:59** FAILED REVIEW **
  
  
  
 1) NOTE: BASE BUILDING PERMIT # 07050361 DOES NOT SHOW
 OR CONTAIN THE ROOM WHICH IS BEING NOTED ON THE PLANS.
 IN FACT PLANS SUBMITTED CLEARLY STATE * GENERATOR FUEL
 TANK ROOM* HOWEVER THIS ROOM DOES NOT ACTUALLY EXISTS
 ON ELECTRICAL OR BUILDING PLANS OF BASE BUILDING.
 THIS ROOM NEEDS TO CONTAIN ALL INFORMATION FOR REVIEW
 UNDER BASE BUILDING OR SEPARATE PERMIT FOR DESIGNS
 UNDER NFPA-70 (2005), 2004 FBC W/ 2007 REVISIONS,
 NFPA-72, NFPA-101, NFPA-30 ETC
 AS NO ELECTRICAL DETAILS SPECIFIC TO ROOM ARE SHOWN
 MANY ITEMS FOR CODE COMPLIANT REVIEW COULD NOT BE DONE.
 THE OTHER ELECTRICAL DETAILS ON PLANS SUCH AS THE ONES
 ON SHEET #3 ARE NOT RELEVANT UNLESS FUEL PUMPS ARE
 GOING TO BE INSTALLED. PLEASE INCLUDE DETAILS ONLY FOR
 NEW SCOPE OF WORK. THE SPECIFIC DETAILS NEED TO
 COORDINATE FOR SCOPE OF WORK AS APPLIED.
 NO RISER DIAGRAM SUBMITTED FOR HOW NEW PANELS ARE BEING
 FED.
 NO FEEDERS, NO GROUNDING, NO LOADS, ETC.
 THE BASE BUILDING PLANS DO NOT CONTAIN THESE SAME
 PANELS AS SHOWN ON THIS SAME SHEET #3.
 MINIMUM PLANS REQUIRED FOR SCOPE OF WORK.
 FBC 106.1.1, 106.1.2, 106.3.5.1.2 (AS ADOPTED BY LOCAL
 AMENDMENTS)
  
 2) NOTE: THE BASE BUILDING AND ALL ELECTRICAL SYSTEMS
 AS WELL AND OTHER SYSTEMS ARE UNDER THE DESIGN AND THE
 RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM UNTIL
 SUCH TIME OF A CERTIFICATE OF OCCUPANCY IS ISSUED. ANY
 WORK DONE ON THIS PROJECT UNDER DESIGN FROM OTHER THAN
 THE BASE BUILDING DESIGNERS OF RECORD SHALL BE REVIEWED
 AND STAMPED WITH A *SHOP DRAWING REVIEW STAMP*. EACH
 SHEET MUST CONTAIN THE STAMP FROM RELEVANT DESIGNER.
  
 3) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR
 ENGINEERING FIRM AS LISTED DOES NOT CORRELATE WITH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE ADJUST AND REVISE TITLE BLOCKS TO COORDINATE
 WITH THE STATE OR PLEASE CONTACT STATE TO REVISE.
 FAC 61G15-23.002, FS 471.023
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  