| 2008-11-20 16:54:59 | ** FAILED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: BASE BUILDING PERMIT # 07050361 DOES NOT SHOW |
| | OR CONTAIN THE ROOM WHICH IS BEING NOTED ON THE PLANS. |
| | IN FACT PLANS SUBMITTED CLEARLY STATE * GENERATOR FUEL |
| | TANK ROOM* HOWEVER THIS ROOM DOES NOT ACTUALLY EXISTS |
| | ON ELECTRICAL OR BUILDING PLANS OF BASE BUILDING. |
| | THIS ROOM NEEDS TO CONTAIN ALL INFORMATION FOR REVIEW |
| | UNDER BASE BUILDING OR SEPARATE PERMIT FOR DESIGNS |
| | UNDER NFPA-70 (2005), 2004 FBC W/ 2007 REVISIONS, |
| | NFPA-72, NFPA-101, NFPA-30 ETC |
| | AS NO ELECTRICAL DETAILS SPECIFIC TO ROOM ARE SHOWN |
| | MANY ITEMS FOR CODE COMPLIANT REVIEW COULD NOT BE DONE. |
| | THE OTHER ELECTRICAL DETAILS ON PLANS SUCH AS THE ONES |
| | ON SHEET #3 ARE NOT RELEVANT UNLESS FUEL PUMPS ARE |
| | GOING TO BE INSTALLED. PLEASE INCLUDE DETAILS ONLY FOR |
| | NEW SCOPE OF WORK. THE SPECIFIC DETAILS NEED TO |
| | COORDINATE FOR SCOPE OF WORK AS APPLIED. |
| | NO RISER DIAGRAM SUBMITTED FOR HOW NEW PANELS ARE BEING |
| | FED. |
| | NO FEEDERS, NO GROUNDING, NO LOADS, ETC. |
| | THE BASE BUILDING PLANS DO NOT CONTAIN THESE SAME |
| | PANELS AS SHOWN ON THIS SAME SHEET #3. |
| | MINIMUM PLANS REQUIRED FOR SCOPE OF WORK. |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2 (AS ADOPTED BY LOCAL |
| | AMENDMENTS) |
| | |
| | 2) NOTE: THE BASE BUILDING AND ALL ELECTRICAL SYSTEMS |
| | AS WELL AND OTHER SYSTEMS ARE UNDER THE DESIGN AND THE |
| | RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM UNTIL |
| | SUCH TIME OF A CERTIFICATE OF OCCUPANCY IS ISSUED. ANY |
| | WORK DONE ON THIS PROJECT UNDER DESIGN FROM OTHER THAN |
| | THE BASE BUILDING DESIGNERS OF RECORD SHALL BE REVIEWED |
| | AND STAMPED WITH A *SHOP DRAWING REVIEW STAMP*. EACH |
| | SHEET MUST CONTAIN THE STAMP FROM RELEVANT DESIGNER. |
| | |
| | 3) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR |
| | ENGINEERING FIRM AS LISTED DOES NOT CORRELATE WITH THE |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. |
| | PLEASE ADJUST AND REVISE TITLE BLOCKS TO COORDINATE |
| | WITH THE STATE OR PLEASE CONTACT STATE TO REVISE. |
| | FAC 61G15-23.002, FS 471.023 |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |