2008-11-20 14:41:36BUILDING PLAN REVIEW
 PERMIT: 08100556
 ADD: 800 CLEMATIS ST
 CONT: SURGE SOLUTIONS
 TEL: (561)309-6030
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) DISCREPANCY BETWEEN THE PERMITED MASTER PLANS SHEET
 A1.01 SITE PLAN AND THE PROPOSED LOCATION ON THE NEW
 PLAN FOR INSTALLATION OF A BOVE GROUND FUEL TANK.
 SHEET# 1 OF THE NEW TANK PERMIT INDICATES THE TANK TO
 BE LOCATED WITHIN A GENERATOR FUEL TANK ROOM IN A
 DIFFERENT LOCATION FROM THE ORIGINAL PERMITTED PLANS.
 THE ORIGINAL PERMITTED PLANS DOES INDICATE A CHILLER
 ENCLOSURE( NOT ROOFED IN).
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) IF THE 2,000 GALLON ABOVE GROUND FUEL TANK IS TO BE
 WITHIN A ROOM THEN SECTION 415.2.2-415.7.2.10 ARETO BE
 MET.
  
 4) IF THE TANK IS TO BE PLACED OUTDOORS THEN THE
 REQUIREMENTS OF 414.6 OUTDOOR STORAGE - SHALL BE IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 5) IF OUTDOORS THE WIND REQUIREMENTS ARE MISSING FROM
 THE PLAN.1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 6) PLANS DO NOT PROVIDE HOW THE TANK WILL BE SUPPORTED
 .
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.