| 2008-11-04 08:37:05 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE INCLUDE NEW OR EXISTING HORNS, STROBES, |
| | HORN/STROBE DEVICES MEETING FBC 11-4.28.1, .2 AND .3. |
| | PLEASE LIST THE HEIGHTS AND LEVELS. |
| | |
| | 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| | THESE WOULD BE FOR NEW AREAS ONLY AND MAY BE SHOWN ON |
| | PLANS FOR TABLE 13-415.2.B |
| | PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND. |
| | ** NEW BEING INSTALLED |
| | |
| | 3) NOTE: PLEASE INCLUDE LIGHTING CONTROLS PER |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. ** NEW BEING INSTALLED |
| | ONLY REQUIRED |
| | |
| | 4) NOTE: THE RISER AS SHOWN ON PLANS IS NOT SHOWN AS IT |
| | EXISTS. IF EXISTING THEN PLEASE INDICATE OTHERWISE THE |
| | REVIEW WILL BE DONE FOR NEW EQUIPMENT UNDER CURRENT |
| | CODES. |
| | 230,220,240 ETC |
| | |
| | 5) NOTE: PLEASE SEE THE CODE SECTION REFLECTED PER |
| | 700.12E IS NOW DIFFERENT UNDER THE CURRENT 2005 NEC. |
| | THE NEW CODE SECTION IS 700.12F. IF THIS HAD BEEN THE |
| | ONLY COMMENT IT WOULD HAVE BEEN REDLINED. PLEASE |
| | CORRECT AT THIS TIME. |
| | |
| | 6) NOTE: PLEASE SEE THE PLANS NEED TO STATE THE |
| | FOLLOWING CODES AS A DESIGN STANDARD AT A MINIMUM. |
| | THESE ARE FOR THIS REVIEWER ONLY. PLEASE BE AWARE OF |
| | ANY COMMENTS FORM OTHER TRADES WHICH MAY HAVE ANY |
| | COMMENTS |
| | |
| | 2004 FBC W/2007 REVISIONS. |
| | 2003 NFPA-101 |
| | 2005 NFPA-70 |
| | |
| | 7) NOTE: PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR |
| | SCOPE OF WORK. AS NO PANEL SCHEDULE WAS SHOWN WITH |
| | CIRCUITING LOADS ETC REVIEW OF THESE ITEMS COULD NOT BE |
| | DONE. PLEASE INCLUDE THE NEW AND EXISTING LOADS ON |
| | PANEL. |
| | 220, 408.4, 215.3, 230.42 ETC |
| | FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION, CLARITY |
| | AND COORDINATION. |
| | |
| | 8) NOTE: PLEASE SUBMIT LIGHTING LEVELS FOR STAIRS UNDER |
| | NORMAL AND EMERGENCY CONDITIONS. PLEASE SEE NFPA-101 |
| | 7.8.1.3, 7.9.1.2, .2.2. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |