| 2008-10-31 17:00:10 | BUILDING PLAN REVIEW |
| | PERMIT: 08100531 |
| | ADD: 1118 25TH STREET #7 |
| | CONT: COMPLETE PROPERTY MANAGEMENT INC. |
| | TEL: (561)626-2778 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 10-31-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | 4) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE INDICATED ON THE DRAWINGS. |
| | |
| | 5) THE INFORMATION FOR THE BUILDING IS NOT LEGIBLE |
| | 106.1.1. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE & EXTENT OF |
| | THE WORK PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM |
| | TO THE PROVISIONS OF THIS CODE AND RELEVANT LAWS, |
| | ORDINANCES, AND RULES AND REGULATIONS AS DETERMINED BY |
| | THE BUILDING OFFICIAL. INDICATE THE SQUARE FOOTAGE OF |
| | THE SPACE AND THE AREA OF THE MEZZANINE. |
| | |
| | 6) THE DRAWINGS NEED TO CLEARLY INDICATE THE TYPE OF |
| | BUILDING PER CHAPTER 6 AND TABLE 503 AND THE USE AND |
| | OCCUPANCY PER CHAPTER 3. |
| | |
| | 7) THE CLEAR HEIGHT ABOVE AND BELOW THE MEZZANINE FLOOR |
| | CONSTRUCTION SHALL NOT BE LESS THAN 7 FEET. FBC 505.1 |
| | SHOWS COMPLIANCE. THE AGGREGATE AREA OF THE MEZZANINE |
| | WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF THE AREA OF |
| | THE ROOM OR SPACE IN WHICH THEY ARE LOCATED. FBC 502.2 |
| | |
| | 8) PLEASE INDICATE THE OCCUPANT LOAD OF THE MEZZANINE |
| | AND THE ENTIRE SPACE ON THE DRAWINGS PER 505.4 TABLE |
| | 1004.1.2 AND TABLE 1607.1 |
| | |
| | 9) PROVIDE AN EXISTING FLOOR PLAN OF THE EXISTING AREA |
| | AND A PROPOSED FLOOR PLAN WITH ALL ELEVATION OF THE NEW |
| | AREA INCLUDING THE FRONT AND SIDES ELEVATIONS. |
| | |
| | 10) 110.4.2 STORAGE & FACTORY- INDUS-TRIAL OCCUPANCIES. |
| | IT SHALL BE THE |
| | RESPONSIBILITY OF THE OWNER, AGENT, PROPRIETOR OR |
| | OCCUPANT OF GROUP S AND GROUP F OCCUPANCIES, OR ANY |
| | OCCUPANCY WHERE EXCESSIVE FLOOR LOADING IS LIKELY TO |
| | OCCUR, TO EMPLOY A COMPETENT ARCHITECT OR ENGINEER IN |
| | COMPUTING THE SAFE FLOOR LOAD CAPACITY. ALL SUCH |
| | COMPUTATIONS SHALL BE ACCOMPANIED BY AN AFFIDAVIT FROM |
| | THE ARCHITECT OR ENGINEER |
| | STATING THE SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN |
| | POUNDS PER SQ FT. THE COMPUTATIONS & AFFIDAVIT SHALL BE |
| | FILED AS A PERMANENT RECORD OF THE BLDG DEPT. |
| | |
| | 11) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART |
| | OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| | PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| | BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| | PLATES OF APPROVED DESIGN WHICH SHALL BE SUPPLIED & |
| | SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| | CONSPICUOUS PLACE IN EACH STORY TO |
| | WHICH THEY RELATE. SUCH PLATES SHALL NOT BE REMOVED OR |
| | DEFACED, & IF LOST, REMOVED THE OWNER OF THE BUILDING |
| | SHALL REPLACE THEM. PLEASE SEE FBC 1603.3 FOR MORE |
| | INFORMATION. |
| | |
| | 12) DETAIL #3 FAILS TO INDICATE THE ATTACHMENT DETAIL |
| | FOR THE FLOOR JOISTS. STATE THE TYPE OF CONNECTIONS FOR |
| | THE FLOOR JOISTS TO THE LEDGER AND THE OUTER WALL. |
| | INDICATE THE GRADE AND SPECIES OF THE FLOOR JOISTS ON |
| | THE PLANS PER FBC 2308.8. THE PLANS FAIL TO SHOW |
| | COLUMNS AND WALLS SUPPORTING THE MEZZANINE. THE |
| | CONNECTION DETAIL FOR THE GUARDRAIL IS ALSO REQUIRED. |
| | |
| | 13) IS THE STAIRWAY BEING ENCLOSED? IF SO, THIS WILL |
| | MAKE THE MEZZANINE AN ENCLOSED AREA. PLEASE SHOW |
| | CLEARLY IF THE WALL AROUND THE STAIRS GOES TO THE DECK |
| | ABOVE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |
| | |